This record type interacts with timer modules.
-------------------------------------------------------------- Field Type DCT Initial Access Modify Rec Proc PP Monitor -------------------------------------------------------------- TORG INLINK Yes 0 No No N/A No OUT OUTLINK Yes 0 No No N/A No VAL SHORT No 0 Yes Yes Yes Yes TSRC RECCHOICE Yes 0 Yes Yes No No PTST RECCHOICE Yes 0 Yes Yes No Yes TEVT SHORT Yes 0 Yes Yes No Yes PREC SHORT Yes 0 Yes Yes No No TIMU RECCHOICE Yes 0 Yes Yes No No MAIN GBLCHOICE Yes 1 Yes Yes No Yes RDT1 FLOAT No 0 Yes Yes No No RDW1 FLOAT No 0 Yes Yes No No PDLY FLOAT Yes 0 Yes Yes No No DUT1 FLOAT Yes 0 Yes Yes No Yes OPW1 FLOAT Yes 0 Yes Yes No Yes DUT2 FLOAT Yes 0 Yes Yes No Yes OPW2 FLOAT Yes 0 Yes Yes No Yes DUT3 FLOAT Yes 0 Yes Yes No Yes OPW3 FLOAT Yes 0 Yes Yes No Yes DUT4 FLOAT Yes 0 Yes Yes No Yes OPW4 FLOAT Yes 0 Yes Yes No Yes DUT5 FLOAT Yes 0 Yes Yes No Yes OPW5 FLOAT Yes 0 Yes Yes No Yes T1DL DOUBLE No 0 Yes Yes No No T1WD DOUBLE No 0 Yes Yes Yes No T2DL DOUBLE No 0 Yes Yes No No T2WD DOUBLE No 0 Yes Yes No No T3DL DOUBLE No 0 Yes Yes No No T3WD DOUBLE No 0 Yes Yes No No T4DL DOUBLE No 0 Yes Yes No No T4WD DOUBLE No 0 Yes Yes No No T5DL DOUBLE No 0 Yes Yes No No T5WD DOUBLE No 0 Yes Yes No No T1TD FLOAT No 0 Yes Yes Yes No T1LD FLOAT No 0 Yes Yes Yes No T2TD FLOAT No 0 Yes Yes No No T2LD FLOAT No 0 Yes Yes No No T3TD FLOAT No 0 Yes Yes No No T3LD FLOAT No 0 Yes Yes No No T4TD FLOAT No 0 Yes Yes No No T4LD FLOAT No 0 Yes Yes No No T5TD FLOAT No 0 Yes Yes No No T5LD FLOAT No 0 Yes Yes No No TRDL FLOAT No 0 Yes Yes No No TDIS SHORT No 0 Yes Yes No Yes --------------------------------------------------------------
--------------------------------------------------------------------------------------- Name Summary Description --------------------------------------------------------------------------------------- TORG Trigger Delay This is a link specifying the location of the trigger delay Origin (input link) value. This must be a constant, a database link, or a channel access link. If TORG is a database link, then TRDL is read from TORG. OUT Output Link This field is used by the device support routines to decide where to send output. VAL Value Field This field is used to force record processing. TSRC Clock Source External or internal PTST Pre-Trigger State Low or high TEVT Event Number To Be Posted On Trigger PREC Display Precision TIMU Timer Units Milli, micro, nano. pico seconds MAIN Maintain on Reboot RDT1 Reboot Delay of 1 RPW1 Reboot Width of 1 PDLY Delay Source to Input DUTn Delay Width For (n=1-5): In timer units. Trigger n OPWn Output Pulse Width (n=1-5): In timer units. For Trigger n TnDL Delay Width For (n=1-5): In seconds. Trigger n TnWD Pulse Width Of (n=1-5): In seconds. Trigger n TnTD Trailing Delay Of (n=1-5): ( TiLD+OPWi ) Trigger n TnLD Leading Delay Of (n=1-5): ( DUTi+TRDL ) Trigger n TRDL Trigger Delay Obtained from trigger delay origin TORG. TDIS Timing Pulse Disable ---------------------------------------------------------------------------------------