Federal ERO-1071 Setup Info --------------------------- - EPICS Files: Federal.st, Federal.db, Federal.adl, Federal_more.adl, Federal_setup.adl, Federal.db.txt (this file). - Federal Box Settings: probe: "scan", scan probes = num_probes <- set in db x.xxx: set this to match prec on adl display show: set all to "yes" units: set to "mm" print: 0, "no", "reading then step" rs232: 19200, 2, "even", "no", "no" - In st.cmd: # Federal digital encoder readout dbLoadRecords("kagApp/Db/Federal.db","P=xxx:,S=s1,C=0,SERVER=serial1",top) - In st_mpfserver.cmd: tyGSMPFInit("serial1", 0, 0, 19200,'E',2,7,'N',"") /* Federal */ - RS-232 connection: db9 db25 --- ---- 2 2 3 3 5 7 - Device needs ctrl-B (STX) (0x02) for reading. No cr or lf necessary.