Device |
Unit |
A16 |
A24 |
A32 |
Interrupt vector |
Interrupt level |
OMS-VME58 |
0 |
0x4000 |
|
|
190 (0xBE) |
5 |
|
1 |
0x5000 |
|
|
191 (0xBF) |
|
|
2 |
0x6000 |
|
|
192 (0xC0) |
|
|
3 |
0x7000 |
|
|
193 (0xC1) |
|
|
4 |
0x8000 |
|
|
194 (0xC2) |
|
|
5 |
0x9000 |
|
|
195 (0xC3) |
|
|
6 |
0xA000 |
|
|
196 (0xC4) |
|
|
7 |
0xB000 |
|
|
197 (0xC5) |
|
|
8 |
0xC000 |
|
|
198 (0xC6) |
|
OMS-VME8/44 |
0 |
0xFC00 |
|
|
180 (0xB4) |
5 |
|
1 |
0xFC10 |
|
|
181 (0xB5) |
|
|
2 |
0xFC20 |
|
|
182 (0xB6) |
|
|
3 |
0xFC30 |
|
|
183 (0xB7) |
|
|
4 |
0xFC40 |
|
|
184 (0xB8) |
|
|
5 |
0xFC50 |
|
|
185 (0xB9) |
|
Allen-Bradley 6008 |
0 |
|
0xC00000 |
|
96 (0x60) |
|
Joerger VSC scaler |
0 |
|
|
0xB0000000 |
200 (0xC8) |
5 |
|
1 |
|
|
0xB0000100 |
201 (0xC9) |
|
SIS 380x multiscaler |
0 |
|
|
0x90000000 |
220 (0xDC) |
6 |
Note 0x90000000 for the SIS380x doesn't work on MVME5100 boards. Suggest 0xA4000000
|
|
1 |
|
|
0x90000800 |
221 (0xDD) |
|
SBS VIPC-616 |
0 |
0x3000 |
|
0xA0000000 |
|
|
|
1 |
0x3400 |
|
0xA2000000 |
|
|
SBS IP-Octal |
0 |
|
|
|
128 (0x80) |
|
|
1 |
|
|
|
129 (0x81) |
|
SBS IP-Unidig |
0 |
|
|
|
116 (0x74) |
|
|
1 |
|
|
|
117 (0x75) |
|
SBS IP-488 |
0 |
|
|
|
104 (0x68) |
|
Acromag IP-330 |
0 |
|
|
|
120 (0x78) |
|
Systran DAC128V |
0 |
|
|
|
|
|
Kinetic Systems 2917 |
0 |
0xFF00 |
|
|
160-163 (0xA0-0xA3) |
|
APS quadEM |
0 |
|
0xF000 |
|
|
|
APS MSL MRD100 |
0 |
|
|
0XB0000200 |
160 (0xA0) |
5 |
HP LaserAxis interferometer |
0 |
0x1000 |
|
|
|
|
HP LaserAxis interferometer |
1 |
0x1100 |
|
|
|
|
Acromag AVME-9440 |
0 |
0x0400 |
|
|
112 (0x70) |
|
Bunch-clock generator |
0 |
0x8C00 |
|
|
|
|
XYCOM-240 |
0 |
0xD000 |
|
|
|
|