Experimental Physics and Industrial Control System
Chestnut, Ronald P. wrote:
Yes. Records are "Active" until all the related processing is done.
Active records are not "refired".
in reply to Emmanuel Mayssat's question:
I just wanted to have confirmation that in the case of a FLNK loop (
2 records FLNK to one another ), the loop stops once before
processing an already processed record.
While Ron is right about this most all the time, there are circumstances
where two records can FLNK each other and cause a loop; both records
must have asynchronous device support for that to occur.
Here's the timeline with two synchronous records, showing how we break
these loops using the record PACT field:
Request to process r1 is made.
dbProcess() checks r1.PACT, finds it false.
r1.process() called:
r1.PACT = true
r1 performs I/O etc according to record type,
calls recGblFwdLink()
r1.FLNK => r2
dbProcess() checks r2.PACT, finds it false,
r2.process() called:
r2.PACT = true
r2 performs I/O etc according to record type,
calls recGblFwdLink()
r2.FLNK => r1
dbProcess() checks r1.PACT, finds it true.
dbProcess() returns
r2.PACT = false
r2.process() returns
r1.PACT = false
r1.process() returns.
However if both records have asynchronous device support, the timeline
changes and we can get into a continuous loop, controlled by the speed
of the device:
Request to process r1 is made.
dbProcess() checks r1.PACT, finds it false.
r1.process() called:
r1.PACT = true
r1 starts I/O operation
r1.process() returns.
r1.device finishes I/O operation,
r1.process() called:
r1 completes I/O processing
calls recGblFwdLink()
r1.FLNK => r2
dbProcess() checks r2.PACT, finds it false,
r2.process() called:
r2.PACT = true
r2 starts I/O operation
r2.process() returns
r1.PACT = false
r1.process() returns.
r2 device finishes I/O operation,
r2.process() is called:
r2 completes I/O processing
calls recGblFwdLink()
r2.FLNK => r1
dbProcess() checks r1.PACT, finds it false,
r1.process() called:
r1.PACT = true
r1 starts I/O operation
r1.process() returns.
r2.PACT = false
r2.process() returns
At this point the IOC will continue to loop between the second and third
paragraphs of that description forever, although the time it takes for
the I/O operation to complete will control how often it loops.
It is necessary to have two or more asynchronous device supports in a
FLNK loop for this situation to occur - with a single asynchronous
record processing will always come back to the original record with the
PACT field set and thus break the loop. Synchronous records in the loop
have no effect on this argument except to increase the stack usage.
Note that the infinite loop will not result in a stack overflow, since
the two paragraphs can never nest - the lockset locking prevents the I/O
completion from happening until after the previous paragraph has come to
the end of its work.
- Andrew
--
There is no S in exprexxo.
- References:
- RE: FLNK loop Chestnut, Ronald P.
- Navigate by Date:
- Prev:
RE: FLNK loop Chestnut, Ronald P.
- Next:
Wago 750 reliability Eric Williams
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
<2006>
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: FLNK loop Chestnut, Ronald P.