We have a client application which attempts to access a PV's elements 0
to 999 . This application is run on two sets of machines. One set
must go through an EPICS gateway to access the PV. The other set does
not do so. The application does not run properly when going through
the gateway because of an out-of-bounds error at element 940. It is
able to access elements all they way up to 999 without issue when there
is no gateway involved.
We were able to track this issue down to a difference in the element
count reported by the originating IOC vs. the gateway using cainfo.
For the gateway case cainfo reports element count 940, but for the
non-gateway case cainfo reports 1000. Using EPICS_CA_ADDR_LIST we
were able to reproduce both element counts on a single machine depending
on whether the gateway or the originating IOC responded. The result is
attached.
Me and my co-workers find this result unexpected and are not sure how to
fix it. Any help would be appreciated please. Thanks for your time.
Sincerely,
Carl Schumann
P.S.: for my co-worker Dehong owner of the hins_ws.py:
The client is hins_ws.py. The PV is PD_LEBT:Inst:WS1.RST1. It is the
out-of-bound error that prevents the Save Result button from generating
a file. Do have any insight about what might be going on here? Thanks.
clx22$ export EPICS_CA_ADDR_LIST=131.225.143.59
clx22$ cainfo PD_LEBT:Inst:WS1.RST1
CA.Client.Exception...............................................
Warning: "Identical process variable names on multiple servers"
Context: "Channel: "PD_LEBT:Inst:WS1.RST1", Connecting to: 131.225.143.59:5064, Ignored: cag-clx-2.fnal.gov:5064"
Source File: ../cac.cpp line 1209
Current Time: Fri May 21 2010 13:20:42.301346264
..................................................................
PD_LEBT:Inst:WS1.RST1
State: connected
Host: hinst1.fnal.gov:5064
Access: read, write
Data type: DBR_FLOAT (native: DBF_FLOAT)
Element count: 1000
clx22$ cainfo PD_LEBT:Inst:WS1.RST1
PD_LEBT:Inst:WS1.RST1
State: connected
Host: cag-clx-2.fnal.gov:5064
Access: read, write
Data type: DBR_FLOAT (native: DBF_FLOAT)
Element count: 940
CA.Client.Exception...............................................
Warning: "Identical process variable names on multiple servers"
Context: "Channel: "PD_LEBT:Inst:WS1.RST1", Connecting to: 131.225.120.203:5064, Ignored: hinst1.fnal.gov:5064"
Source File: ../cac.cpp line 1209
Current Time: Fri May 21 2010 13:25:01.625878952
..................................................................
clx22$
- Replies:
- RE: PV's element count differs though CA gateway Jeff Hill
- Navigate by Date:
- Prev:
Re: genSub to aSub conversion emmanuel_mayssat
- Next:
RE: PV's element count differs though CA gateway Jeff Hill
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: genSub to aSub conversion Andrew Johnson
- Next:
RE: PV's element count differs though CA gateway Jeff Hill
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
<2010>
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024