1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 <2016> 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 <2016> 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: Motor record with encoders |
From: | Mark Rivers <[email protected]> |
To: | "'Henrique Almeida'" <[email protected]>, "[email protected] Talk" <[email protected]> |
Date: | Thu, 18 Feb 2016 18:59:04 +0000 |
Yes the motor record can update REP when all motors are stopped. If you are using a “Model 2” or “Model 3” driver that does callbacks when the motor is idle then the record
will automatically process and update. If you are using a “Model 1” driver then you need to write to the STUP field to force the record to read the status. Mark From: [email protected] [mailto:[email protected]]
On Behalf Of Henrique Almeida Hello, is the motor record currently able to update the encoder position ("REP" PV) while all motors are stopped ? |