Hi Kay,
The solution which you gave to me, writing column to PV, worked fine. However, there is another problem.
My script is not only to write a one column but there is a little more logic and commands.
And commands run in different order than I expect.
This is my script:
##################################################
from org.csstudio.opibuilder.scriptUtil import PVUtil
from array import array
if PVUtil.getLong(pvs[0]) > 0:
# Get the table content
table = widget.getTable()
content = table.getContent()
# print content
# Get table's column 1,2 (counting from 0) into val,dwel
val = [float(r[1]) for r in content]
dwel = [float(r[2]) for r in content]
pvs[6].setValue(1) # Reset
pvs[10].setValue(0) # Output off -- this line makes problem
pvs[7].setValue(1) # clear all lists
if PVUtil.getString(pvs[11]) == 'VOLT':
pvs[4].setValue(5) # set current limit
pvs[1].setValue(array('d', val)) # write voltage list to device
pvs[3].setValue(array('d', dwel)) # set steps
elif PVUtil.getString(pvs[11]) == 'CURR':
pvs[5].setValue(5) # set voltage limit
pvs[2].setValue(array('d', val)) # write current list to device
pvs[3].setValue(array('d', dwel)) # set steps
pvs[8].setValue(1) # set count
pvs[9].setValue(1) # set direction
pvs[10].setValue(1) # set output on
pvs[12].setValue('LIST') # set output mode list
##################################################
When I comment the line pvs[10].setValue(0) then everything is OK.
Otherwise, the last command “set output mode list” is before “set output on”.
This is what is printed:
1. Reset
2. Set output off
3. Clear list
4. (assuming ‘volt’) set current limit
5. write voltage list
6. write step list
7. write count
8. set direction
9. set output mode list (missing set output on)
10. (get output) - this I think is RBV from command 2
11. set output on
12. (get current limit) RBV
13. (get output) RBV
Why is that and what would be the best solution to run it in the proper sequence?
I have to first “set output on” and then “set output mode list” which is actually executing all.
It does not make sense to execute, when output is off….
Regards
--
Tomasz Brys
Integrated Control System
European Spallation Source ERIC
On 05/07/17:27 17:44, "Kasemir, Kay" <[email protected]> wrote:
Hi:
> Michael Davidsaver <[email protected]>
>http://www.aps.anl.gov/epics/tech-talk/2016/msg01173.php
>Is this what you're looking for? To write eg. an array of double?
Michael already linked to the basics of writing an array.
The other missing piece might be constructing the plain array in the Jython code.
In your example, you never fetched any column from the table, you just kept writing "i", the scalar loop index, to a PV.
Plus PVUtil.writePV("$(PREFIX):ListVo...) would perform the potentially slow PV connection in the script, i.e. on the UI thread.
Try this:
# Have this script with two PVs attached to the table widget
#
# pvs[0]: Something like loc://do_write_the_column(0), triggering the script execution
# pvs[1]: That array PV to which you want to write the column, NOT triggering the script
from org.csstudio.opibuilder.scriptUtil import PVUtil
from array import array
if PVUtil.getInt(pvs[0]) > 0:
# Get the table content
table = widget.getTable()
content = table.getContent()
# Get table's column 2 (counting from 0) into col
col = []
for row in content:
col.append(row[2])
# Write that column as a double[] array to the array PV
pvs[1].setValue(array(col), 'd')
Now have your button write 1 to loc://do_write_the_column(0)
Note that only the first PV must trigger the script execution, not the second one, because otherwise the script writing to the array PV would trigger the script which writes the array PV which triggers the script to write the array PV etc.
-Kay
On 07/05/2017 04:14 PM, Tomasz Brys wrote:
> Hi,
> I need help.
> I have an OPI BOY. I created a table Nx3, (Nrows, 3 columns), N can be from 1 to 200.
> User can modify the table and when is ready press the button to write the whole column of the table to PV
> The PV is type of aao , size 200. Of course, the table can have less than 200 elements.
> What would be the easiest way to do this?
> I tried something like that, create an Action Button and as an action I execute such a script:
>
> from org.csstudio.opibuilder.scriptUtil import PVUtil
> from array import array
>
> tab = display.getWidget("Table")
>
> row = tab.getTable().getRowCount()
> for i in range(1, row):
> PVUtil.writePV("$(PREFIX):ListVolt", i) # - this works but write always one element [0]
> print i
>
> My question:
> How I can write one column of a table to PV which is type of aao?
> Is it possible to write the whole column at once? Or I have to do it element by element?
> Any help will be appreciated.
>
> Regards
> --
> Tomasz Brys
> Integrated Control System
> European Spallation Source - ERIC
>
>
>
- Replies:
- Re: help - writing a table column from OPI BOY to PV Kasemir, Kay
- References:
- help - writing a table column from OPI BOY to PV Tomasz Brys
- Re: help - writing a table column from OPI BOY to PV Michael Davidsaver
- Re: help - writing a table column from OPI BOY to PV Kasemir, Kay
- Navigate by Date:
- Prev:
ioc crashing while using asyn & modbus Gary Croke
- Next:
Re: ioc crashing while using asyn & modbus Mark Rivers
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: help - writing a table column from OPI BOY to PV Tomasz Brys
- Next:
Re: help - writing a table column from OPI BOY to PV Kasemir, Kay
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
<2017>
2018
2019
2020
2021
2022
2023
2024