1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: StreamDevice return state error |
From: | "Barrett \(US\), Patrick E via Tech-talk" <tech-talk at aps.anl.gov> |
To: | "pearsonmr at ornl.gov" <pearsonmr at ornl.gov>, "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov> |
Date: | Tue, 28 Jun 2022 17:20:44 +0000 |
I tried this and get the same error. The Alarm state is not getting set in the record. It’s almost like the StreamDevice is handling/returning the error without putting the bad request into the record itself.
Any other suggestions? Thanks, Patrick From: Pearson, Matthew <pearsonmr at ornl.gov>
Hi, I’m assuming you mean that the STATE_RTN record should go to ERROR state if there’s a problem with the RCV_STATE record? One way to do this is to use the STAT and/or SEVR fields of the RCV_STATE record. They should indicate a problem if either of those is !=0, and so you could do something like: record(mbbi, "RCV_STATE") { field(DESC, "SYSTEM:STATE P01") field(DTYP, "stream") field(SCAN, "I/O Intr") field(INP, "@simCmd.proto readSystemState(STATE_RTN) $(PORT) 0") field(ZRST, "STANDBY") field(ZRVL, "0") field(ONST, "OPERATE") field(ONVL, "1") field(TWST, "SELFTEST") field(TWVL, "2") field(UNSV, "INVALID") field(FLNK, “RCV_CALC”) } record(calcout, “RCV_CALC”) { field(INPA, “RCV_STATE.STAT”) field(CALC, “A!=0?1:0”) field(OOPT, “Every Time”) field(DOPT, “Use CALC”) field(OUT, “STATE_RTN PP”) } record(bi, "STATE_RTN") { field(DESC, "State Return") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(ZNAM, "OK") field(ONAM, "ERROR") field(VAL, 0) field(PINI, 1) } Or, something along those lines. Depending on which client you use, the RCV_STATE record itself should also indicate there’s a problem, and you can also display the STAT and/or SEVR fields if necessary. Cheers, Matt From: Tech-talk <tech-talk-bounces at aps.anl.gov>
On Behalf Of Barrett (US), Patrick E via Tech-talk I am working to simulate a SCPI type device with an IOC. I am using I/O Intr records to read in the SCPI and set the state of the mbbi record. The IOC should return ERROR if an error
occurs, such as if an invalid state is requested. I can see the error message in the IOC when an invalid state is requested, but do not know how to capture the error in the protocol file or db setup to send a return string of “ERROR”. The error I get is when sending the IOC “SYSTEM:STATE MONITOR” is: ’… RCV_STATE: Record does not accept input "MONITOR"’ Proto definition: readSystemState { in "SYSTEM:STATE %s"; out "%(\$1)s"; } Record definition: record(mbbi, "RCV_STATE") { field(DESC, "SYSTEM:STATE P01") field(DTYP, "stream") field(SCAN, "I/O Intr") field(INP, "@simCmd.proto readSystemState(STATE_RTN) $(PORT) 0") field(ZRST, "STANDBY") field(ZRVL, "0") field(ONST, "OPERATE") field(ONVL, "1") field(TWST, "SELFTEST") field(TWVL, "2") field(UNSV, "INVALID") } record(bi, " STATE_RTN ") { field(DESC, "State Return") field(DTYP, "Soft Channel") field(SCAN, "Passive") field(ZNAM, "OK") field(ONAM, "ERROR") field(VAL, 0) field(PINI, 1) } Patrick Barrett Software Engineer The Boeing Company |