1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: calc type record question |
From: | "Kasemir, Kay via Tech-talk" <tech-talk at aps.anl.gov> |
To: | "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>, "Meddage, Varuna" <meddage at phys.ksu.edu> |
Date: | Tue, 1 Nov 2022 16:13:38 +0000 |
The length of the CALC field is limited something around 80 characters.
Try to simplify your _expression_, for example by removing some parentheses that are good for readability but not strictly necessary.
From: Tech-talk <tech-talk-bounces at aps.anl.gov> on behalf of Meddage, Varuna via Tech-talk <tech-talk at aps.anl.gov>
Sent: Tuesday, November 1, 2022 11:08 AM To: tech-talk at aps.anl.gov <tech-talk at aps.anl.gov> Subject: [EXTERNAL] calc type record question Hi,
I have following "calc" type record in one of my .db files. =============================================================== record(calc,"$(detector)_wib$(crate)0$(wib)/calc") { field(SCAN,"5 second") field(CALC,"((A>=4.6&&A<=5.2)&&(B>=4.6&&B<=5.2)&&(C>=1.75&&C<=1.80)&&(D>=3.2&&D<=3.4)&&(E>=0.7&&E<=2.0))?1:0") field(INPA,"$(detector)_wib$(crate)0$(wib)/vcc") field(INPB,"$(detector)_wib$(crate)0$(wib)/v1") field(INPC,"$(detector)_wib$(crate)0$(wib)/v2") field(INPD,"$(detector)_wib$(crate)0$(wib)/v3") field(INPE,"$(detector)_wib$(crate)0$(wib)/v4") field(DESC,"") field(HIHI,"") field(HIGH,"") field(LOW,"") field(LOLO,"") field(MDEL,"-1") field(ADEL,"-1") field(OOPT,"Every Time") field(PREC,"6") } =============================================================== When I run the EPICS, then I get an error message saying "String is too long" complaining about the _expression_, I inserted inside the "CALC" field in this record. But when I reduced the number of input PVs of this record from 5 to 4 and rewrite the _expression_ inside "CALC" field, then there is no error. Is there maximum number of input PVs, that I can use inside a "calc" type record ? Any help to understand this issue is highly appreciated. Thanks Varuna Meddage |