1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: question |
From: | Andrew Johnson via Tech-talk <tech-talk at aps.anl.gov> |
To: | "japanisverylittle at hotmail.com" <japanisverylittle at hotmail.com>, tech-talk <tech-talk at aps.anl.gov> |
Date: | Fri, 5 May 2023 11:32:36 -0500 |
Hi Tomas, On 5/5/23 11:18 AM,
japanisverylittle--- via Tech-talk wrote:
how to explain this? Why does Input_1 run twice at 10 Hz?The original intention was to show an example where two records with SCAN=.1 second (i.e. Output_1 and Calculation_2) would both ask for the Input_1 record to process using the PP (Process Passive) mechanism that record links provide, thus Input_1 would be triggered twice in every 10Hz cycle. However there is a mistake in the diagram; the Output_1.DOL link needs to be marked with the PP flag but as drawn it is flagged with NPP instead, so as drawn the Output_1 record will never actually request the Calculation_1 record to be processed at all, thus the Input_1 record will only process at 10Hz. Was that what you were asking? - Andrew -- Complexity is free, it's Simplicity that takes work. |