LEDA Vacuum System Approach
 | Use Capfast to create the hierarchical description of the database - subsystem, device, component, signals
|
 | Use Capfast to configure the process flow and data flow - making all SCAN, FLNK, soft INP/OUT, NPP/PP, CALC, and HIGH for BO visible on the schematic.
|
 | From the Capfast produced database - create an Access database
|
 | In Access - enter configuration fields: hw INP/OUT, LINR, DTYP, EGUF, EUGL, ZNAM, ONAM etc
.
|
 | Load the database from Capfast then the database from Access - EPICS will create records if there is no existing record - or overwrite any fields in the last loaded database
|
|