Experimental Physics and Industrial Control System
I'm getting the eror message:
abDrv: SET_MODE failed link 0
when I run abAutoConfig(0) before iocInit()
rather than executing
abConfigScanListAscii(0,"/bin/drrfConfig.ab",1)
where drrfConfig.ab has the following:
1 0 Full
The setup is 1746-A7 (7-slot allen-bradley crate)
I've got an SLC 5/05 (model No. 17747-L553) cpu in
slot 0 and a 1747-DCM in slot 5 (8-word table).
The VXI crate has a niCpu030 and a
6008-SV1R Allen-Bradley Scanner. I am loading a database
but no records. When I do load a database with a
DCM record or a SLCDCM device support the adapter
the AB driver thinks that the scanner OFFLINE, and
I do not get this SET_MODE error.
The SET_MODE error is issued from drvAb link_init()
routine when an attempt fails to put the scanner
into run mode.
Any help would be appreciated.
- Thanks,
Kristi Luchini
- Navigate by Date:
- Prev:
Re: EPICS web pages at LANL Steve Lewis
- Next:
Re: EPICS web pages at LANL Bill McDowell
- Index:
1994
1995
1996
1997
1998
<1999>
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: Scan Record Tim Mooney
- Next:
Alpha Scientific power supply controller support Coles Sibley
- Index:
1994
1995
1996
1997
1998
<1999>
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024