Garrett,
I had a similar problem; a misbehaving CAMAC link would mess up the mv177
IOC record scan while waiting for a response from the link. To avoid this I
modified (LANL/CEBAF camacLib.c revised 03-12-96 by mlr) the 2992 driver
code. In summary, the link timeout was shortened from about 1 second per
CNAF to about 120 ms for slot-30 write CNAFS, and to twice the link
propogation time for non-slot-30 CNAFS.
For a hardware solution, Jorway Corporation makes a Model 176 Serial Byte
Highway Bypass module. We use these to automatically bypass powered-down
crate-groups to keep the main highway working. Perhaps you can use one of
these to bypass the 750 keV section of the link when the generator is turned
off.
--
Paul Sichta
Princeton Plasma Physics Laboratory
609-243-3477
----- Original Message -----
From: Garrett D. Rinehart <[email protected]>
To: <[email protected]>
Sent: Wednesday, February 16, 2000 3:30 PM
Subject: camac crate init
> I've got a kind of a peculiar Camac here. I'm wondering if any of you
> can help me out.
>
> The Camac is driven by the Hytec 2992 (driver from CEBAF/TJNAF). I'm
> using EPICS_3.13.0b11 on an MV172.
>
> The crate sits in a very nasty (electrically) environment and goes
> "brain-dead" every once in a while. To get around this, I just execute
> the "camacCrateInit" routine from a subroutine record every ten
> seconds. This works very well, generally. Unfortunately, the crate is
> run off a generator ('cus it's in a room that floats at 750keV) and
> it's shut down when the machine is not running. The only problem there
> is that it brings the VME crate to its knees waiting to hear from the
> Camac and, as a result of repeated failed attempts to init the crate,
> eventually crashes. (Note that the mv167 was much more rhobust about
> this than the mv172, but both crash from it.)
>
> My questions to all of you are:
> 1) Is there a better way to do this?
> 2) What is that better way?
>
> Thanks very much in advance.
>
>
> Garrett Rinehart
> Intense Pulsed Neutron Source
> Argonne National Laboratory
> 9700 S. Cass Ave
> Argonne, IL 60439
> (630)252-6561
>
>
- References:
- camac crate init Garrett D. Rinehart
- Navigate by Date:
- Prev:
Re: camac crate init Andrew Johnson
- Next:
Anyone using/supporting e2sr? Brian Bevins
- Index:
1994
1995
1996
1997
1998
1999
<2000>
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: camac crate init Andrew Johnson
- Next:
Anyone using/supporting e2sr? Brian Bevins
- Index:
1994
1995
1996
1997
1998
1999
<2000>
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024