Hi -
I am trying to force a binary output record to come up in a
specific state at IOC initialization. The device is an XVME-240, and I
want the outputs to come up "high" at startup. Here is what I tried:
record (bo,"mybo"){
field(PINI,"1")
field(VAL,"1")
field(SCAN,"Passive")
field(DTYP,"XY240_BO")
field(OUT,"#C0 S24")
field(ZNAM,"0")
field(ONAM,"1")
}
I set PINI to "1" to force processing at iocInit time, and I set the VAL
field to "1" to get the output to start out "high". But this doesn't
work -- the output comes up "low" at startup.
I also tried to use the DOL field:
record (bo,"mybo"){
field(PINI, "1")
field(DOL, "1")
field(SCAN, "Passive")
field(DTYP, "XY240_BO")
field(OUT, "#C0 S24")
field(ZNAM, "0")
field(ONAM, "1")
}
But that didn't work either.
I also tried this last setup without setting PINI at all. No cigar.
I am using EPICS Version R3.13.0.beta.11.
Quoting from the EPICS Record Reference Manual, Ch. 8 Binary Output,
Section 8 Record Support Routines:
"If DOL is a constant, then VAL is initialized to 1 if its value is
nonzero or initialized to 0 if DOL is zero, and UDF is set to FALSE."
I also read quite a bit of the tech-talk archive, especially two recent
threads about "VxWorks global variable device support" and "support for
output records" which discussed in some detail concerning what happens
to output records at startup. But somehow I am still missing something.
So what am I doing wrong?
thanks,
Steve Pate
()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()()
Stephen Pate Department of Physics office: 505-646-2135
Box 30001, Dept. 3D dept: 505-646-3831
New Mexico State University fax: 505-646-1934
[email protected] Las Cruces NM 88003 home: 505-382-6880
- Replies:
- Re: forcing binary output value at initialization Andrew Johnson
- Re: forcing binary output value at initialization pate
- Navigate by Date:
- Prev:
serial device support john sinclair
- Next:
Re: forcing binary output value at initialization Andrew Johnson
- Index:
1994
1995
1996
1997
1998
1999
<2000>
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
serial device support john sinclair
- Next:
Re: forcing binary output value at initialization Andrew Johnson
- Index:
1994
1995
1996
1997
1998
1999
<2000>
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024