Hi,
I am using Bob Dalesio's save_restore/dbrestore (bumpless reboot) software and
notice that the save files, which it writes, follow the current working
directory of the console shell. This means that, if one invokes
create_monitor_set during ioc boot and then later issues a "cd xxx" at the ioc
shell prompt, a new set of save files will be written in the new directory as
soon as one of the monitored PVs changes. On rebooting the ioc, the database
reverts to the state before the "cd"!
Was this behaviour a design decision? I think that saving the full path of the
save file, rather than just its name, in the chlist structure of save_restore.c
would correct this behaviour, but maybe there are arguments to the contrary ...
David
--
[email protected]
_/_/_/ _/ _/_/_/ Beamline Group, SLS Project
_/ _/ _/ Paul Scherrer Institute
_/_/ _/ _/_/ CH-5232 Villigen-PSI
_/ _/ _/ Tel: +41 56 310 3616
_/_/_/ _/_/_/ _/_/_/ Fax: +41 56 310 3294
- Navigate by Date:
- Prev:
Where can I find the caMath? guobao shen
- Next:
Re: save_restore Query Ned Arnold
- Index:
1994
1995
1996
1997
1998
1999
2000
<2001>
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Where can I find the caMath? guobao shen
- Next:
Re: save_restore Query Ned Arnold
- Index:
1994
1995
1996
1997
1998
1999
2000
<2001>
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024