1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  2025  Index 1994  1995  1996  1997  1998  1999  2000  2001  <20022003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  2025 
<== Date ==> <== Thread ==>

Subject: Re: seq 1.9.4
From: Rozelle Wright <[email protected]>
To: [email protected]
Date: Fri, 22 Mar 2002 12:04:14 -0700
I'm sure you are all tired of this thread, but the exact
symptoms we had are the following: 
We logged onto an ioc with telnet.
We killed and restarted the sequencer as many times as we wanted to in
the same telnet session,
but when we logged off of telnet, the ioc died.
We would never see a problem if we had a serial interface to the ioc.
This problem went away when we removed the line that closed the log file.
Rozelle