Experimental Physics and Industrial Control System
Rok Sabjan wrote:
Hello!
I'm dealing with some stepper motor control and would like to use
auxiliary outputs of the OMS 58 motor controller card for setting the
stepper driver to all windings off mode. Has this been attempted before?
I have looked into motor record, but was unable to find any
implementation of that functionality.
Do you think this is possible?
br
Rok
I've been using the VME8-8 instead of the OMS 58 but I use this feature
for boosting the drive current to the motors. I'm using version 4.41 of
the motor record and there is one gotcha as far as I know .... see
below. Note that the pre-move command has a space as part of the
command. I found that this was required to get the pre-move to work
properly. So, you should check that your signals work with your database.
record(motor,"Moto1r") {
field(DESC,"US motor")
field(DTYP,"OMS VME8/44")
field(PREM," AF1")
field(POST,"AN1")
}
Marty Smith
Argonne National Lab.
APS - Controls Group
- References:
- OMS 58 and auxiliary outputs Rok Sabjan
- Navigate by Date:
- Prev:
Re: OMS 58 and auxiliary outputs David Maden
- Next:
Has anyone ever written a tool... Benjamin Franksen
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
<2003>
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: OMS 58 and auxiliary outputs David Maden
- Next:
CA Put Logging bug fixing. Vladis Korobov
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
<2003>
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024