1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: PV gateway
From: Ralph Lange <[email protected]>
To: Motoki Ooi <[email protected]>
Cc: tech-talk <[email protected]>
Date: Tue, 11 Jan 2005 10:55:10 +0100
To avoid ambiguity, channel names must be unique to a client. Your client obviously "sees" channels both directly as well as through the CA Gateway.

Possible ways to fix this problem include
- Setting up the environment for your client so that it sees the IOC either direct or through the Gateway (but not both) - based on IP networks
- Setting up the environment for the Gateway so that it does not see (and forward) IOCs in the local network - based on IP networks
- Setting up the PV list of the Gateway so that it does not forward channels from a local IOC - based on channel names


The correct solution depends on the structure of your network and the design of your application. You will have to properly identify your data sources and sinks (i.e. CA servers and clients) and their location in your network(s) to find out who should be supposed to see what through which path (Gateway or direct).

Once you know what you want to achieve, the CA Reference Manual (the sections on Environment Variables and WANs) and the Gateway Users Guide (sections on Access Security and Gateway Configurations) will provide you with the details of how to set up your clients and/or Gateways.

Hope this helps,
Ralph


Motoki Ooi wrote:


Hello all

I'm tring to use PV gateway but I have one trouble.
Once use PV gateway with small number of record, PV gateway works well.
But when use with large number of records ( over 200 ),
some records are connected to PV gateway but other records connecet to
EPICS IOC directry.
It means some record say
`DB CA Link Exception: "Identical process variable name on multiple
servers",
contest "Channel: "archive:wf83", Connecting to :
ccnet307.tokai.jaeri.go.jp:5064, Ignored : 133/53/55/207:5064" '
other records say
`DB CA Link Exception: "Identical process variable name on multiple
servers",
contest "Channel: "archive:wf44", Connecting to : 133.53.55.207:5064,
Ignored : ccnet307.tokai.jaeri.go.jp:5064" '.
ccnet307 is EPICS IOC and 133.53.55.207 is PV gateway server.


Thanks


Motoki Ooi



--
Ralph Lange               [email protected]     Fon: +49 30 6392-2117
BESSY Controls Group      www.bessy.de             Fax:      ...   -4859


References:
PV gateway Motoki Ooi

Navigate by Date:
Prev: PV gateway Motoki Ooi
Next: CA links and EPICS Records user routines Andy Foster
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: PV gateway Motoki Ooi
Next: CA links and EPICS Records user routines Andy Foster
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  <20052006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024