1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 <2005> 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 <2005> 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Initial STAT and SEVR for soft ai and ao records |
From: | Marty Kraimer <[email protected]> |
To: | [email protected] |
Cc: | [email protected] |
Date: | Wed, 23 Feb 2005 07:40:53 -0600 |
On Wednesday 16 February 2005 20:42, Marty Kraimer wrote:
If all that is desired to to make the record not be in alarm after initialization then just set
field(SEVR,"NO_ALARM") field(STAT,"NO_ALARM") field(UDF,"0")
In the record instance definition.
Note that you can leave out SEVR and STAT as these are the default values anyway.
However, at least with 3.13.9 this doesn't work. The record (a bo) is still UDF/INVALID after booting.
Ben
field(STAT,DBF_MENU) { prompt("Alarm Status") special(SPC_NOMOD) menu(menuAlarmStat) initial("UDF") } field(SEVR,DBF_MENU) { prompt("Alarm Severity") special(SPC_NOMOD) menu(menuAlarmSevr) initial("INVALID") }