For anyone considering using a Sorenson DLM16-250EM9E Power Supply (serial
communication option), be advised of the following:
I had problems getting the device to communicate. Initially, I could get no
response from the device. After examining the section on RS485 communication,
which notes that S1 (remote/local) must be set to remote, I configured the
switch so and power-cycled the device. It then responded to one command - but
only one command. After the first response, the device became silent.
Repeating the power-cycle gave the same results.
I called Elgar at 11:30am on 6/10/05 and left a message requesting a return
call.
Elgar did not return my call by 5:00pm so I called back.
I talked with a tech support person and he told me that a line-feed will lock
up the device and that I should terminate commands with a carriage-return
only. I asked if he thought this behavior was acceptable and pointed out that
noise could cause the supply to lock up forever. He thought it was quite
acceptable.
The serial communication uses SCPI, which is an attempt to standardize the
protocol. Hopefully, other Sorenson models don't have the same broken
command-processing engine.
--
John Sinclair
- Navigate by Date:
- Prev:
RE: LabVIEW RT interface with EPICS Liyu, Andrei
- Next:
Re: Open source Real-time Oss / open source OS D. Peter Siddons
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
RE: RTEMS on Diamond Systems Prometheus/ EPICS IOC on eCos Jeff Hill
- Next:
Re: rtems if_dc ethernet driver Eric Norum
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024