Hi all,
since quite a long time I have problems with enums though the CA
gateway. They did not update their value correctly even though time and
status are OK.
I found that the problem occurs only when an alh is also connected to
the enum through the gateway.
Diagnostic:
If an alh is connected, all data is handled differently. A different gdd
type is used (dbr_stsack_string instead of value). In
gateVcData::setEventData(), the gateway copies the incoming value to an
already existing dbr_stsack_string container. See debug output:
[Aug 03 16:53:03] gateVcData::setEventData DZ-mbbo1
(1) ***********************************************************
dd (incoming) at=16[value] pt=5[aitEnum16]
----------dump This=0x8074000---------
dimension=0 app-type=16 Scalar
prim-type=aitEnum16(aitEnumEnum16) value=1 ref-count=1
total-bytes=44, data-size=2, element-count=1
LocalDataFormat
--------------------------------------
(4) ***********************************************************
event_data(after) at=35[dbr_stsack_string] pt=12[aitContainer]
----------dumping container:
----------dump This=0x80de9d0---------
dimension=1 app-type=35 Container
prim-type=aitContainer(aitEnumContainer) ref-count=1
total-bytes=188, data-size=136, element-count=3
destructor=0x8075f08
(0) 0x80dea80 first=0 count=3
Managed Flat LocalDataFormat
total in container = 3
----------dump This=0x80de9fc---------
dimension=0 app-type=19 Scalar
prim-type=aitUint16(aitEnumUint16) value=1 ref-count=1
total-bytes=44, data-size=2, element-count=1
LocalDataFormat NoReferencing
--------------------------------------
----------dump This=0x80dea28---------
dimension=0 app-type=20 Scalar
prim-type=aitUint16(aitEnumUint16) value=2 ref-count=1
total-bytes=44, data-size=2, element-count=1
LocalDataFormat NoReferencing
--------------------------------------
----------dump This=0x80dea54---------
dimension=0 app-type=16 Scalar
prim-type=aitString(aitEnumString)
this=0x80dea54 string=0x80e9420<OFF>, length=3, buf length=4, type=Allocated
ref-count=1
total-bytes=48, data-size=12, element-count=1
LocalDataFormat NoReferencing
--------------------------------------
Here, the input value (1 in this case) is NOT converted to the correct
string (still OFF instead of ON). The string keeps its value from
connection time.
Bugs:
gddApplicationTypeTable::smartCopy() does not work correctly then
copying application type "value" to "dbr_stsack_string" if the value is
an enum. In this copy, gdd::set() is called, which in turn (through
aitConvertFromNet() and a conversion table) calls
aitConvertStringEnum16() but the enum string table is never passed.
Thus, it is not possible to use smartCopy() to copy enum to string.
Additionally, without the enum string table or when the number is out of
bounds, aitConvertStringEnum16() writes the string representation of the
number to a local string buffer but never copies that buffer to the
destination string. This is clearly a bug in gdd.
aitConvertFixedStringEnum16(), however, does it correctly.
The enum string table is stored externally gateVcData::pv_data. In my
opinion, it should be stored in the gdd if the gdd is an aitEnum16.
Now, gateVcData::setEventData() must handle conversions enums to
container (or string) separately, passing the enum string table to the
conversion function. But it doesn't. This is a bug in the gateway.
Is this conversion to a string really necessary? It does not happen if
no alarm handler is connected. An other side effect of the conversion is
that DOUBLE values are rounded to only 6 significant digits if an alh is
watching them. I think, data should be stored in its native type
wherever possible.
I will report more when I have solved the problem.
So far my advice: Don't connect alh to the same gateway as your "normal"
clients.
Dirk
--
Dr. Dirk Zimoch
Swiss Light Source
Paul Scherrer Institut
Computing and Controls
phone +41 56 310 5182
fax +41 56 310 4413
- Replies:
- RE: bugs in gateway and gdd Kenneth Evans, Jr.
- Re: bugs in gateway and gdd Ralph Lange
- Navigate by Date:
- Prev:
Re: 3.14.7 - build on solaris - error Zoltan Kakucs
- Next:
RE: bugs in gateway and gdd Kenneth Evans, Jr.
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
device supports for EVG200, VME-EVR-200, VME-EVR-RF-200, GUN-TX, GUN-RC 黄松
- Next:
RE: bugs in gateway and gdd Kenneth Evans, Jr.
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024