Hi Ge,
Three things I'd suggest (based on my experience with 100 series hardware):
1) make sure your EVG is properly "seated" in the crate. Even if LEDs are
on, I've found that board can be incorrectly seated. This happened with
64x VME crates.
2) ensure the top rotary dial is set to '2' and the lower rotary dial is
set to '0'
3) change your card number from '4' to '0' if you only have one EVG
Step (3) may not be necessary to get it working.
You need to get a '0' return code from EgConfigure before you can get
any further.
The same suggestions apply to EVR (rotaries at '1' and '8', change
card to '0'). For EVR only, check that jumpers are set to '5' as
is documented on the board itself.
Dayle Kotturi
LINAC Coherent Light Source
Stanford Linear Accelerator Center
On Tue, 20 Sep 2005, Lei Ge wrote:
> Hello,
>
> I'm testing the event generator EVG200, but my IOC failed to probing the
> event-generator board. Could somebody give me some suggestions? Thank you
> very much.
> ---------------------------------------------------------
> EgConfigure(4,0x2000)
> value = -1 = 0xffffffff = prsrv_cast_client + 0xff0f7b3f
> ErConfigure(6,0x1800,164,5)
> value = -1 = 0xffffffff = prsrv_cast_client + 0xff0f7b3f
>
> cd "/home21/home/leige/epicsApp/dbd"
> value = 0 = 0x0
> dbLoadDatabase("baseApp.dbd")
> devApsEg: Failure probing for event generator... Card disabled
> devApsEr: Failure probing for event receiver... Card disabled
> value = 0 = 0x0
> dbLoadDatabase("evgevr.dbd")
> value = 0 = 0x0
>
> ----------------------------------------------------------------
> Best wishes,
>
> Ge
>
>
- Replies:
- Re: Failure probing for event generator Korhonen Timo
- References:
- Failure probing for event generator Lei Ge
- Navigate by Date:
- Prev:
Re: EDM <--> MEDM display-file translators Dayle Kotturi
- Next:
Re: EDM <--> MEDM display-file translators wether
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Failure probing for event generator Lei Ge
- Next:
Re: Failure probing for event generator Korhonen Timo
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
<2005>
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024