EPICS Home

Experimental Physics and Industrial Control System


 
1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: SIMM mode for mbbiDirect record
From: Kay-Uwe Kasemir <[email protected]>
To: Vladimir Sirotenko <[email protected]>
Cc: [email protected]
Date: Thu, 07 Dec 2006 17:09:29 -0500
Hi:

You're right, it's wrong.
When I look at the sources for rec/mbbiDirectRecord.c, there's this:

static long readValue(pmbbiDirect)
struct mbbiDirectRecord *pmbbiDirect;
{
...
if (pmbbiDirect->simm == menuSimmYES){
status=dbGetLink(&(pmbbiDirect->siol),
DBR_ULONG,&(pmbbiDirect->sval),0,0);
if (status==0){
pmbbiDirect->val=(unsigned short)pmbbiDirect- >sval;
pmbbiDirect->udf=FALSE;
}
status=2; /* don't convert */
}
%%%%%%%% I think an 'else' is missing here %%%%%%%%%
if (pmbbiDirect->simm == menuSimmRAW){
status=dbGetLink(&(pmbbiDirect->siol),
DBR_ULONG,&(pmbbiDirect->sval),0,0);
if (status==0){
pmbbiDirect->rval=pmbbiDirect->sval;
pmbbiDirect->udf=FALSE;
}
status=0; /* convert since we've written RVAL */
} else {
status=-1;
%%%%%%%% because you end up here with SIMM=YES: %%%%%%%%%%%%%%%%
recGblSetSevr(pmbbiDirect,SOFT_ALARM,INVALID_ALARM);
return(status);
}
...


-Kay

On Dec 7, 2006, at 16:47 , Vladimir Sirotenko wrote:

record(longin,"CTL_VS/SET") {
field(DTYP, "Soft Channel")
field(SCAN, "1 second")
field(FLNK, "CTL_VS/MBBI")
field(VAL,"1")
field(PINI,"YES")
}
record(mbbiDirect,"CTL_VS/MBBI") {
field(DTYP, "Raw Soft Channel")
field(INP, "2")
field(SCAN, "Passive")
field(NOBT, "16")
field(SHFT, "0")
field(SIMM, "YES")
field(SIOL, "CTL_VS/SET")
field(FLNK, "CTL_VS/LONGIN")
}
record(longin,"CTL_VS/LONGIN") {
field(DTYP, "Soft Channel")
field(INP, "3")
field(SCAN, "Passive")
field(SIMM, "YES")
field(SIOL, "CTL_VS/SET")
}


Replies:
Re: SIMM mode for mbbiDirect record Kay-Uwe Kasemir
Re: SIMM mode for mbbiDirect record Andrew Johnson
References:
SIMM mode for mbbiDirect record Vladimir Sirotenko

Navigate by Date:
Prev: SIMM mode for mbbiDirect record Vladimir Sirotenko
Next: Re: SIMM mode for mbbiDirect record Kay-Uwe Kasemir
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: SIMM mode for mbbiDirect record Vladimir Sirotenko
Next: Re: SIMM mode for mbbiDirect record Kay-Uwe Kasemir
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  <20062007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024