Hello:
Thanks for tracking this down!
500 is a value that happens to work right now for all the
ControlLogix PLCs
at the SNS, but that is based on luck, not a full understanding of
the real limit.
The header file ether_ip.h has some comments
about my (failed) attempts to figure this buffer limit business out.
I found no specific buffer limit in the protocol specification.
Tests with an AllenBradley ControlLogix PLC went like this:
When reading elements of an SINT array, I could pick the
_response_ packet size pretty much to the byte by asking
for more or fewer array elements (SINT==8bit byte).
From that, it seemed that the PLC could send a response
of 538 bytes, not one byte more.
So in that case, it seemed obvious that the PLC _response_ was
limited to 538 bytes, while you now found a _request_ limit of 548.
It's been unclear to me if the limit of 538 in the response
applies to the total byte count for the whole
protocol wrapper + status codes + meta info + actual data,
or if some of the protocol wrappings don't count.
-Kay
On Jun 29, 2007, at 16:21 , Mike Forster wrote:
Hi folks,
Just an update on our EtherIP with CompactLogix use:
We are communicating smoothly with the PLC at this point after
sorting out an anomaly.
We saw that when a record scan list became long (too many records
with the same scan rate), all the elements in that scan list would
stop responding. Eventually we traced this down to the
EIP_buffer_limit which was the default 500. This limit at 500
allows data to be sent that is 554 bytes long. After some trial
and error we found that the PLC responded correctly if the data
sent was 548 bytes long or less. When we set EIP_buffer_limit to
494 our problems went away.
Mike Forster with John Dobbins
LEPP
Cornell University
- References:
- Re: Ethernet/IP Device Support and CompactLogix Mike Forster
- Navigate by Date:
- Prev:
Re: Ethernet/IP Device Support and CompactLogix Mike Forster
- Next:
GPIB Ethernet gateway recommendation Jiro Fujita
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
<2007>
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025
- Navigate by Thread:
- Prev:
Re: Ethernet/IP Device Support and CompactLogix Mike Forster
- Next:
GPIB Ethernet gateway recommendation Jiro Fujita
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
<2007>
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
2025