1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Monitors |
From: | "Thomas Birke" <[email protected]> |
To: | [email protected] |
Cc: | [email protected] |
Date: | Thu, 17 Sep 2009 21:51:05 +0200 |
-----Ursprüngliche Nachricht-----
Von: Szalata, Zenon M. <[email protected]> Gesendet: 17.9.'09, 21:23 Is it possible to setup a "longin" record to generate a monitor each time it is processed regardless whether the VAL value changes or not? If so, how do I do it?
Just set MDEL to -1 That'll do the job... Thomas