1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | CA problem w EPICS 3.14.11 & VxWorks 6.7 |
From: | "GOURNAY Jean-Francois" <[email protected]> |
To: | <[email protected]> |
Date: | Tue, 24 Nov 2009 15:37:52 +0100 |
Hello, We have 2 IOCs running EPICS 3.14.11 with VxWorks 6.7.
Any record on an IOC with a CA link on a record
located in the other IOC stays UDF=1 forever. This problem arises with EPICS_CA_AUTO_ADDR_LIST=
YES. With EPICS_CA_AUTO_ADDR_LIST=NO and
EPICS-CA-ADDR-LIST= … it works. But we would like to avoid to have this
parameter to “NO” and having to maintain the host list in
ADDR-LIST. Especially in the case where: On IOC1 : EPICS-CA-ADDR-LIST=<IP IOC2> And on IOC2: EPICS-CA-ADDR-LIST=<IP IOC1> (needed for CA links in both directions) We have “CA beacon routing … ECONNREFUSED”
on the 1rst booted IOC. We did’nt have this problem with the previous release. This problem arises also with CA links between
VxWorks an Linux. On the other hand, no problem with CA links between 2
Linux IOCs Thanks Jeff (I think it is probably a problem for you
. . .) J.F. Gournay CEA Saclay IRFU/SIS |