Hi Keiko,
UP and DOWN refer to the direction that the alarm severity (0 to 3) of the PV or group is changing. NO_ALARM (0) is the lowest and INVALID_ALARM (3) the highest. So DOWN_MAJOR will only activate the command when the severity changes from INVALID to MAJOR. UP_MAJOR only activates the command when the change is from NO_ALARM to MAJOR or MINOR to MAJOR.
Stephanie Allison
> -----Original Message-----
> From: [email protected] [mailto:[email protected]] On Behalf
> Of Keiko Ezawa
> Sent: Monday, April 11, 2011 11:41 AM
> To: [email protected]
> Subject: Alarm Handler Configuration
>
> Hello,
>
> I am trying to configure the alarm handler to send a notification to a pager by using
> $SEVRCOMMAND. I have a channel, IG1:STATON, and when it is turned off or tripped
> off, the alarm handler alarms. However, I don't get the notification to my pager.
>
> $SEVRCOMMAND DOWN_MAJOR send_alhmail.pl [email protected] 555 1
>
> When I change DOWN_MAJOR to UP_MAJOR, I receive a notification. Could someone
> please explain when/how to use UP_MAJOR and DOWN_MAJOR?
>
> Thank you very much,
>
> Keiko
- References:
- Alarm Handler Configuration Keiko Ezawa
- Navigate by Date:
- Prev:
Alarm Handler Configuration Keiko Ezawa
- Next:
Re: vxworks BSP sysBusToLocalAdrs not support PCI space Dirk Zimoch
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Alarm Handler Configuration Keiko Ezawa
- Next:
How to execute CSS/BOY directly in OPIruntime mode ? patard
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
<2011>
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024