Hi Pierrick,
Some questions:
- Are sure this device talks Modbus ASCII, not Modbus RTU?
- I don't understand the difference between port wirte1VAL and write1CLS that you have created. They are created identically, i.e. they write to the same address, so why did you create 2 ports?
drvModbusAsynConfigure("write1VAL","RFTunerPort",0x01,0x10,0x0031,1,0,0,"ProportionAir1")
drvModbusAsynConfigure("write1CLS","RFTunerPort",0x01,0x10,0x0031,1,0,0,"ProportionAir1")
- Since you are writing a single register why did you use Modbus function code 0x10 (=16=write multiple registers), rather than function code 6 (write single register)?
- What is the evidence that the write is successful?
Write operations read a response from the Modbus server. In your case you are getting the following:
2012/09/28 10:49:49.964 modbusInterpose::readIt, LRC error
2012/09/28 10:49:49.964 drvModbusAsyn::doModbusIO port write1CLS error calling writeRead, error=, nwrite=9/9, nread=0
That implies it is getting no response. But to be sure you should turn on asynTrace on the underlying RS-485 port:
asynSetTraceIOMask("RFTunerPort",0,4)
asynSetTraceMask("RFTunerPort",0,255)
That will show you what is being written and read by the underlying serial port, and hopefully help to pin down the problem.
Mark
-----Original Message-----
From: [email protected] [mailto:[email protected]] On Behalf Of Pierrick M Hanlet
Sent: Friday, September 28, 2012 11:41 AM
To: [email protected]
Subject: modbus 2.4
Hi,
I have an ioc (base 3.14.11) using modbus 2.4 in which I'm controlling ProportionAir
Modbus Serial OPV1 proportional air valves over RS485 serial. In my st.cmd file,
I have:
modbusInterposeConfig("RFTunerPort",2,1000,0)
drvModbusAsynConfigure("read1ADDR", "RFTunerPort",0x01,0x03,0x0000,1,0,86400000,"ProportionAir")
drvModbusAsynConfigure("read1VALU", "RFTunerPort",0x01,0x03,0x0031,1,0,86400000,"ProportionAir")
drvModbusAsynConfigure("read2ADDR", "RFTunerPort",0x02,0x03,0x0000,1,0,86400000,"ProportionAir")
drvModbusAsynConfigure("read2VALU", "RFTunerPort",0x02,0x03,0x0031,1,0,86400000,"ProportionAir")
drvModbusAsynConfigure("write1VAL","RFTunerPort",0x01,0x10,0x0031,1,0,0,"ProportionAir1")
drvModbusAsynConfigure("write1CLS","RFTunerPort",0x01,0x10,0x0031,1,0,0,"ProportionAir1")
drvModbusAsynConfigure("write2VAL","RFTunerPort",0x02,0x10,0x0031,1,0,0,"ProportionAir2")
drvModbusAsynConfigure("write2CLS","RFTunerPort",0x02,0x10,0x0031,1,0,0,"ProportionAir2")
And, in my database, I have:
record(ai,"MICE-RF-TUNE-01:READADDR") {
field(DESC,"Read address")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(INP,"@asyn(read1ADDR,0, 60)MODBUS_DATA")
}
record(ai,"MICE-RF-TUNE-01:READVALU") {
field(DESC,"Read value")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(INP,"@asyn(read1VALU,0,36000)MODBUS_DATA")
}
record(ai,"MICE-RF-TUNE-02:READADDR") {
field(DESC,"Read address")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(INP,"@asyn(read1ADDR,0, 60)MODBUS_DATA")
}
record(ai,"MICE-RF-TUNE-02:READVALU") {
field(DESC,"Read value")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(INP,"@asyn(read1VALU,0,36000)MODBUS_DATA")
}
###############################################################################
### Write functions
###############################################################################
### Unit 1
record(ao,"MICE-RF-TUNE-01:WRITEVALU") {
field(DESC,"Write open 0%")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(VAL, "0x0000")
field(OUT,"@asynMask(write1VAL,0,16)MODBUS_DATA")
}
record(ao,"MICE-RF-TUNE-01:WRITE000") {
field(DESC,"Write open 0%")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(VAL, "0x0000")
field(OUT,"@asynMask(write1CLS,0,16)MODBUS_DATA")
}
### Unit 2
record(ao,"MICE-RF-TUNE-02:WRITEVALU") {
field(DESC,"Write open 0%")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(VAL, "0x0000")
field(OUT,"@asynMask(write2VAL,0,16)MODBUS_DATA")
}
record(ao,"MICE-RF-TUNE-02:WRITE000") {
field(DESC,"Write open 0%")
field(SCAN,"Passive")
field(DTYP,"asynInt32")
field(VAL, "0x0000")
field(OUT,"@asynMask(write2CLS,0,16)MODBUS_DATA")
}
===================================================
My problem is that I can successfully write, but I cannot read from the devices.
Whether I read or write, I get messages:
After a successful write:
2012/09/28 10:49:49.964 modbusInterpose::readIt, LRC error
2012/09/28 10:49:49.964 drvModbusAsyn::doModbusIO port write1CLS error calling writeRead, error=, nwrite=9/9, nread=0
2012/09/28 10:49:49.964 MICE-RF-TUNE-01:WRITE000 devAsynInt32 process error
An attempt to read results in:
2012/09/28 11:37:55.103 MICE-RF-TUNE-01:READVALU devAsynInt32 process read error
I keep reading the modbus 2.4 Driver Support for Modbus Protocol under EPICS, but I'm clearly
missing something. I don't understand why I get an error on a successful write, and I don't
understand why I cannot read at all. Please help.
Thanks,
Pierrick
===================================================
"Whether you think you can or think you can't, either way, you are correct"
-- Henry Ford
_________________________________________________________________________
Pierrick Hanlet
IIT/Fermilab
+1-630-697-8758 (FNAL)
+1-312-567-5745 (IIT)
+1-630-697-8758/+44-7-948-860-1978 (US/UK mobile)
- Replies:
- RE: modbus 2.4 Pierrick M Hanlet
- References:
- modbus 2.4 Pierrick M Hanlet
- Navigate by Date:
- Prev:
modbus 2.4 Pierrick M Hanlet
- Next:
RE: modbus 2.4 Pierrick M Hanlet
- Index:
1994
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
<2012>
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
modbus 2.4 Pierrick M Hanlet