1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 <2013> 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 <2013> 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: genesys power supply IOC |
From: | James F Ross <[email protected]> |
To: | Jiro Fujita <[email protected]> |
Cc: | EPICS Tech Talk <[email protected]> |
Date: | Mon, 22 Apr 2013 11:38:08 -0400 |
James,Port 8003 is correct on this one. This is mostly based upon genesys IOC that I got from Stephanie Allison at SLAC.The problem is most likely that your start up command is calling device called "GEN8-180-88Z" (which is what the Genesys that STAR HFT has), where as somehow, it is expecting "07G-ECD-BL08" (which I don't know where it come from). You may want to double-check the db and dbd files. I seem to remember something of that.I will check a bit more in detail on what I have on the test machine at Creighton...On Apr 22, 2013, at 5:20 PM, James F Ross <[email protected]> wrote:I believe it uses TCP (it communicates via an ethernet connection). Below is my start up script. I got this IOC after it had been compiled on another machine, so it is quite possible I missed changing something.
#!../../bin/linux-x86/genesys
cd ../..
dbLoadDatabase("dbd/genesys.dbd")
genesys_registerRecordDeviceDriver(pdbbase)
## Location of stream protocol files
epicsEnvSet "STREAM_PROTOCOL_PATH", "iocBoot/soft-iocps/"
dbLoadRecords("db/genesysPSAll.db")
drvAsynIPPortConfigure("GEN8-180-88Z", "130.199.60.184:8003",0,0,0)
iocInit()
# Start sequences
seq(&psControl,"ps=GEN8-180-88Z")I know the IP is right for the drvAsynIPPortConfigure, but I don't know if 8003 is correct.
Thank youJamesOn Mon, Apr 22, 2013 at 11:05 AM, Mark Rivers <[email protected]> wrote:
Can you explain the interface to the power supply? It is serial, TCP, etc.
How have you configured the asyn port?
Can you send your startup script?
Mark
________________________________
From: [email protected] [[email protected]] on behalf of James F Ross [[email protected]]
Sent: Monday, April 22, 2013 9:45 AM
To: EPICS Tech Talk
Subject: genesys power supply IOC
Hello all,
I'm trying to set up an IOC for a genesys power supply. It compiles, but when I try to run st.cmd I get the following errors (showing up in red after iocInit):
2013/04/22 09:37:58.974089 _main_ Businterface '07G-ECD-BL08' not found for '07G-ECD-BL08:Curr'
2013/04/22 09:37:58.974603 _main_ 07G-ECD-BL08:Curr: Can't attach to bus 07G-ECD-BL08 -1
2013/04/22 09:37:58.974715 _main_ 07G-ECD-BL08:Curr: Record initialization failed
Segmentation fault
I'm using asyn version 4.21, StreamDevice version 2.6, epics 3.14.12.1, and sequencer 2.0.12.
From what I've been able to find, this seems to be a problem between StreamDevice and asyn. I originally had aysn 4.13 before getting 4.21 and trying that. Neither solved the issue though. Anyone have any experience with this kind of issue?
Thanks!
James