1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Re: Proper initialisation of Motor Record .RMP value
From: Ron Sluiter <[email protected]>
To: <[email protected]>
Date: Tue, 22 Oct 2013 09:49:45 -0500
Hello Peter,

The EPICS motor record has no allowance for rolling over the DBF_LONG (epicsInt32) RMP field.

If the application and the motion control system support it, then one way to avoid the whole problem would be to reduce the motor resolution field (MRES).  For example, if this was a ACS SPD-32M mini-stepping motor driver module configured for 8 mini-steps per full step, you could reduce that to 6 mini-steps per full step and adjust the MRES according. Again, only if the application can support the reduced resolution.

Ron


On 10/21/2013 9:55 PM, Peter Linardakis wrote:

We're pretty new at controlling motors using EPICS and we've run into a few small issues.  After a crate reboot, some of a bank of 28 motors end up with a motor.RMP value that is quite close to the signed 32-bit integer limit (both at max and min ends).  If we then try move the motor more than the difference, the motor just stops.  We're not running a complicated setup, we just home the motors using limit switches.  We do not use encoders at this time.

My question is,
how do we properly initialise the .RMP value to some known value, probably zero?  At this stage of the game, we're not looking to use an autosave module or similar.

Regards
Peter

Dr Peter Linardakis

Accelerator Research and Development Engineer

Nuclear Physics | Research School of Physics and Engineering

Australian National University

e: [email protected]

p: (02) 6125 2862 f: (02) 6215 0748



References:
Proper initialisation of Motor Record .RMP value Peter Linardakis

Navigate by Date:
Prev: Re: how to put value to other record in subroutine record Martin L. Smith
Next: caQtDM Mezger Anton Christian
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024 
Navigate by Thread:
Prev: RE: Proper initialisation of Motor Record .RMP value Mark Rivers
Next: Prosilica GX1050 - dual port GigE and areaDetector Piccoli, Luciano
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  <20132014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024