If the Ethernet port is disconnected then CA does not work. I think if you set EPICS_CA_AUTO_ADDR_LIST=NO and EPICS_CA_ADDR_LIST=localhost it will work, but I am not certain.
You could also just plug the Ethernet cable into a cheap switch with nothing else connected to it :-)
Mark
________________________________
From:
[email protected] [
[email protected]] on behalf of Julio Calvo [
[email protected]]
Sent: Thursday, November 28, 2013 9:53 AM
To: techtalkForo
Subject: All Pvs disconnected
Hello,
I have move a computer from my lab, it was working perfectly, it was connected to internet, now, this computer is in other place without internet connection for security reasons. I have open the IOC, pvs are ok after dbl. But CSS GUI appears as disconnected, any idea?. I have done this several times and I never found this problem. Do I have to configure something?.
Thanks.
Julio.