1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 <2014> 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 <2014> 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Processing a record a in loop |
From: | David Michel <[email protected]> |
To: | "Dalesio, Leo" <[email protected]> |
Cc: | EPICS mailing list <[email protected]> |
Date: | Wed, 3 Sep 2014 14:55:30 +0100 |
If you need a longer scan rate - you can modify menu.dbd. I think that the instructions in the Application Developer's Guide covers this.
Bob
________________________________________
From: [email protected] [[email protected]] on behalf of Mark Rivers [[email protected]]
Sent: Wednesday, September 03, 2014 8:08 AM
To: David Michel; EPICS mailing list
Subject: RE: Processing a record a in loop
What is the maximum/typical time between when you send a query and receive a response?
You should be able to set the timeout to a value just longer than the maximum and then you can process the record with any fixed rate (1 seconds, 10 seconds, etc.). The record will be busy (PACT=1) if the next scan interval happens before the reply from the previous one. So it will not keep sending query messages, it will wait for a reply before proceeding.
What does your protocol file look like? Is it a single query per response, etc.?
Mark
________________________________
From: [email protected] [[email protected]] on behalf of David Michel [[email protected]]
Sent: Wednesday, September 03, 2014 6:02 AM
To: EPICS mailing list
Subject: Processing a record a in loop
Hi All,
I'm using StreamDevice to talk to a custom device that doesn't support I/O interrupt so one has to keep sending commands to it to get status information.
Problem is that after a while (~ couple of hours), the device's buffer fills up and doesn't reply anymore. Increasing the ReplyTimeOut improves things slightly, but the problem still eventually occurs.
One potential solution would be to send the next command only once the previous one has returned in a loop (instead of using a set frequency).
Making the record FWD link to itself doesn't seem to do it... I started something using purely database trickery with a FANOUT record set with a fixed SCAN field and disabling it depending on whether the streamdevice record has finished processing or not... but it's getting messy
Is there an elegant way of doing this?
David