1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 <2016> 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 <2016> 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Modbus 2.5 How to read a INT32_BE array from a modbus function |
From: | Philippe Laurent <[email protected]> |
To: | "[email protected]" <[email protected]> |
Date: | Tue, 2 Feb 2016 08:37:12 +0000 |
Hello,
I try to read a INT32_BE array from a modbus function into a Waveform using dtyp = asynInt32Array. I get a array of long in the waveform, but the data are not correctly read from modbus. It looks like, the driver constitutes a long with : modbus index 0 + modbus index 1-> waveform data[0] modbus index 1 + modbus index 2-> waveform data[1] modbus index 2 + modbus index 3-> waveform data[2] ... Instead of : modbus index 0 + modbus index 1-> waveform data[0] modbus index 2 + modbus index 3-> waveform data[2] modbus index 3 + modbus index 4-> waveform data[3] My record is : record(waveform, $(EQPT):PostMortemRaw2) { field(DTYP, "asynInt32ArrayIn") field(DESC, "input modbus data") field(NELM, "50") field(FTVL, "LONG") field(SCAN, "I/O Intr") field(INP, "@asyn($(EQPT):PostMortemRd2 0)INT32_BE") } My modbus function is : drvAsynIPPortConfigure("LBEC-DCCT31","172.16.60.231:502",0,0,1) modbusInterposeConfig("LBEC-DCCT31",0,300,2) drvModbusAsynConfigure("LBEC-DCCT31:PostMortemRd2","LBEC-DCCT31",1,3,228,100,6,2000,"PLC")