1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024  Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  <20172018  2019  2020  2021  2022  2023  2024 
<== Date ==> <== Thread ==>

Subject: Limit flags not set on motor IOC restart
From: <[email protected]>
To: <[email protected]>
Date: Wed, 12 Apr 2017 13:00:34 +0000

Hi,

 

I’m a developer working on the Ibex project at the ISIS neutron source. When setting up some new Galil motors on an instrument, one of our team was surprised when restarting the IOC cleared the high limit flag.

 

On inspection of the motor record, this seems to be because the limit flag is only set when the limit switch is hit and the motor is moving out of range (correct CDIR field). As the CDIR field is read-only, it can’t be autosaved so we don’t see a way of preserving state of the limit flag when the IOC is restarted.

 

Can anyone suggest a way of preserving the state of the limits short of modifying motorRecord.cc?

 

Many thanks,

Adrian


Replies:
Re: Limit flags not set on motor IOC restart Torsten Bögershausen

Navigate by Date:
Prev: RE: Writing Area Detector Monitor Iain Marcuson
Next: Re: Limit flags not set on motor IOC restart Torsten Bögershausen