1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 <2017> 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 <2017> 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: Question about autosave ? |
From: | "Mooney, Tim M." <[email protected]> |
To: | lzf neu <[email protected]>, "[email protected]" <[email protected]> |
Date: | Tue, 2 May 2017 16:58:57 +0000 |
Hi Zhefu,
save_restoreSet_SeqPeriodInSeconds() limits the period to be >= 10 seconds. I think you're trying to use autosave as either an archiver, or a data-acquisition system. It's not suitable for either of those purposes. If you have an application that needs this, another tech-talk message describing the requirement will likely get more helpful replies. Tim Mooney ([email protected]) (630)252-5417
Beamline Controls Group (www.aps.anl.gov) Advanced Photon Source, Argonne National Lab From: [email protected] [[email protected]] on behalf of lzf neu [[email protected]]
Sent: Tuesday, May 02, 2017 11:12 AM To: [email protected] Subject: Question about autosave ? hi,
I am new user of autosave and I have two questions to consult you:
1) My PV value refresh every seconds and I want to record them in one minute. As for test, I set one minute generate 60 sequence files, and then check up each files the time intervales. The following lines are segment of my st.cmd file:
save_restoreSet_NumSeqFiles(60) ##//number of sequence files: 60
save_restoreSet_SeqPeriodInSeconds(1) ##// sequence file per second iocInit create_monitor_set("auto1.req",1,"P=RSIS:") ##//begin save record per second however, only 10 files generated (from auto1.sav0 to auto1.sav9 ), and the time intervals of pv value between each file are different (auto1.sav0 and auto1.sav1 are 8 seconds; auto1.sav1 and auto1.sav2 are 12 seconds; auto1.sav2 and auto1.sav3 are 8 seconds.......and
so on.). I have no idea the limit time invervals that the autosave can record and the limit sequence files number.
2) Can autosave list all my PV value during 60 seconds with timestamp in one single file and how to do ?
Thanks in advanced and any help will be appreciated ! Zhefu
|