1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 <2021> 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 <2021> 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Autosave PVs showing up as INVALID(UDF_ALARM) |
From: | "Mooney, Tim M. via Tech-talk" <tech-talk at aps.anl.gov> |
To: | "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>, Iain Marcuson <iain.marcuson at sydortechnologies.com> |
Date: | Wed, 3 Feb 2021 19:58:48 +0000 |
Hi Iain,
You could try writing to the PROC field to verify that processing the record clears the UDF field. If it does, then you could set the TPRO field in the database, and reboot, to check that the fanout record is actually processing the record.
Tim Mooney (mooney at anl.gov) (630)252-5417
Beamline Controls Group (www.aps.anl.gov) Advanced Photon Source, Argonne National Lab From: Tech-talk <tech-talk-bounces at aps.anl.gov> on behalf of Iain Marcuson via Tech-talk <tech-talk at aps.anl.gov>
Sent: Wednesday, February 3, 2021 1:11 PM To: tech-talk at aps.anl.gov <tech-talk at aps.anl.gov> Subject: Autosave PVs showing up as INVALID(UDF_ALARM) I am using autosave in an IOC. Several PVs show up as INVALID(UDF_ALARM). Autosave is set to restore in pass 1, and the PVs appear to be in the autosave .sav files. In addition, I use a series of fanout records to try to force processing of the PVs, although I again get the Undefined status. Are there any items I can check to try to resolve this?
Thank you,
Iain Marcuson Software Engineer, Sydor Technologies 585.278.1168 | www.SydorTechnologies.com Skype: iain.marcuson at sydorinstruments.com
|