1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Strangeness in ai/mbbiDirect with StreamDevice on PINI |
From: | Ralph Lange via Tech-talk <tech-talk at aps.anl.gov> |
To: | EPICS Tech Talk <tech-talk at aps.anl.gov> |
Date: | Tue, 27 Jun 2023 08:50:08 +0200 |
I suspect what you are seeing results from the asyn port not being
connected at the time of the IOC's initial scan.
Firstly, the name "StatusRegister" suggests to me that this value
should be read more than once on IOC startup.
imo. for robust operation some care should be taken anytime when
IOC and device don't share a power switch.
I try to avoid PINI with such devices, and instead use SCAN="10 second"
as a starting point for values which change slowly or only on device
power cycle.