1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 <2023> 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: LINK_ALARM in records |
From: | Florian Feldbauer via Tech-talk <tech-talk at aps.anl.gov> |
To: | tech-talk at aps.anl.gov |
Date: | Fri, 14 Jul 2023 10:39:22 +0200 |
Hey again,I found the issue. All records have a db-link in their SDIS field to a bo record.
This bo record switches on/off the power supply of the device, so if this is set to 0 communication with the device does not work.
The record was set to 1 during initialization but still in UDF_ALARM state which was causing the LINK_ALARM for all other records.
Cheers, Florian On 7/14/23 10:27, Florian Feldbauer via Tech-talk wrote:
Hey all, I have a strange behaviour I haven't seen before. In my IOC all records are set to STAT = LINK_ALARM and SEVR = INVALID.I checked the code of the device support, that is used, but there are only conditions when a record is set to READ_ALARM or WRITE_ALARM.Is there any condition in the record processing itself, where a record can be set to LINK_ALARM?Base 7.0.4.1 is used. The records have a DB_LINK in their SDIS field and some have a FLNK. Cheers, Florian