1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 <2025> | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 <2025> |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: IOC, QServ, and AMSG / alarm.message |
From: | Aqeel Alshafei - STFC UKRI via Tech-talk <tech-talk at aps.anl.gov> |
To: | Michael Davidsaver <mdavidsaver at gmail.com> |
Cc: | "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov> |
Date: | Mon, 17 Feb 2025 16:20:54 +0000 |
Hello Michael,
I have pulled the new commits.
I have tried putting "servr":"MS", in mbbiDirect. I tried using both NAMSG and AMSG on in different places of the pv link.
it does not set alarm.message from AMSG.
In addition, I have tried to put AMSG and NAMSG on a normal PV without input, output or forward link. alarm message is not being set from AMSG.
we would like to have to set AMSG for normal PVs and PVs with links.
below is the test database file I have used for testing. I have added a Calc PV that just increment from 0 to 5 with High alarm set to major when value = 5. However, the alarm message string is not set
record(calc, "$(P):$(R):COUNTER") {
field(VAL, "0")
field(INPA, "5")
field(CALC, "VAL = A? 0: VAL+1")
field(HIGH, "5")
field(HSV, "MAJOR")
field(AMSG, "COUNTER IN AN ALARM STATE")
field(SCAN, "1 second")
}
record(calcout, "$(P):$(R):CALC") {
field(INPA, "0x101")
field(CALC, "A")
field(SCAN, "1 second")
}
record (mbbiDirect, "$(P):$(R):SIMULATED") {
field("DESC", "mbbiDirect from calcout")
field(INP,{pva:{pv:"$(P):$(R):CALC", serv: "MS", proc:"CP"}})
}
record(bi, "$(P):$(R):SIMULATED:B0") {
field(INP, {pva:{pv:"$(P):$(R):SIMULATED.B0", proc:"CP"}})
field(ZNAM, "OFF")
field(ONAM, "ON")
field(OSV, "MAJOR")
field(AMSG, "I AM IN AN ALARM STATE")
}
Regards
Aqeel
ISIS Controls
From: Michael Davidsaver <mdavidsaver at gmail.com>
Sent: 16 February 2025 00:27 To: Alshafei, Aqeel (STFC,RAL,ISIS) <Aqeel.Alshafei at stfc.ac.uk> Cc: tech-talk at aps.anl.gov <tech-talk at aps.anl.gov>; Finch, Ivan (STFC,RAL,ISIS) <ivan.finch at stfc.ac.uk> Subject: Re: IOC, QServ, and AMSG / alarm.message Hello Aqeel,
> field(INP,{pva:{pv:"$(P):$(R):CALC", proc:"CP"}}) Try setting the "sevr" key to "MS". > field(INP,{pva:{pv:"$(P):$(R):CALC", sevr:"MS", proc:"CP"}}) I have also updated PR #100, however this is only a change to the test code, which was not testing everything I thought it was. On 2/14/25 07:53, Aqeel Alshafei - STFC UKRI wrote: > Hello Michael, > > I have switched the test IOC to use pvxs. I've pulled the changes from https://urldefense.us/v3/__https://github.com/epics-base/pvxs/pull/100__;!!G_uCfscf7eWS!Z6EvnRv0uZpu2-5tpfa-eWbruUmdHDvYFuD2e3Hqz8btrWMPr7Mbd5da1kY-Kh2iqsPVIsllxL7xenGFhtxHi3Xfqg$ <https://urldefense.us/v3/__https://github.com/epics-base/pvxs/pull/100__;!!G_uCfscf7eWS!Z6EvnRv0uZpu2-5tpfa-eWbruUmdHDvYFuD2e3Hqz8btrWMPr7Mbd5da1kY-Kh2iqsPVIsllxL7xenGFhtxHi3Xfqg$> > > the alarm.message is not set based on AMSG field. alarm.message string value set to "STATE" then alarm is Minor or Major. > AMSG was set only when the record/PV is in the invalid state. I also tried NMSG field, it behave the same as AMSG, except when PV is invalid is set the alarm.message to "UDF" > > so, alarm.message is set when alarm.severity = 3 AND alarm.status = 2. Otherwise, it does not use the AMSG field and set the string value "STATE" > > the database below should be able to reproduce what I am encountering. a quick way to make the bi record invalid is to set proc to true instead of "CP" then the alarm.message would be set. > > record(calcout, "$(P):$(R):CALC") { > field(INPA, "0x101") > field(CALC, "A") > field(SCAN, "1 second") > } > > record (mbbiDirect, "$(P):$(R):SIMULATED") { > field("DESC", "mbbiDirect from calcout") > field(INP,{pva:{pv:"$(P):$(R):CALC", proc:"CP"}}) > } > > record(bi, "$(P):$(R):SIMULATED:B0") { > field(INP, {pva:{pv:"$(P):$(R):SIMULATED.B0", proc:"CP"}}) > field(ZNAM, "OFF") > field(ONAM, "ON") > field(OSV, "MAJOR") > field(NAMSG, "I AM IN AN ALARM STATE") > } > > > Best Regards > > Aqeel AlShafei > ISIS Controls > > > ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------ > *From:* Tech-talk <tech-talk-bounces at aps.anl.gov> on behalf of Michael Davidsaver via Tech-talk <tech-talk at aps.anl.gov> > *Sent:* 13 February 2025 21:53 > *To:* Finch, Ivan (STFC,RAL,ISIS) <ivan.finch at stfc.ac.uk> > *Cc:* tech-talk at aps.anl.gov <tech-talk at aps.anl.gov> > *Subject:* Re: IOC, QServ, and AMSG / alarm.message > Hi Ivan, > > On 2/13/25 08:21, Ivan Finch - STFC UKRI via Tech-talk wrote: > > Hello, > > > > We have setup a simple IOC with bi records triggered by forward links such as the following: > > What you are trying to do should work. > > Can you test with: https://urldefense.us/v3/__https://github.com/epics-base/pvxs/pull/100__;!!G_uCfscf7eWS!Z6EvnRv0uZpu2-5tpfa-eWbruUmdHDvYFuD2e3Hqz8btrWMPr7Mbd5da1kY-Kh2iqsPVIsllxL7xenGFhtxHi3Xfqg$ <https://urldefense.us/v3/__https://github.com/epics-base/pvxs/pull/100__;!!G_uCfscf7eWS!Z6EvnRv0uZpu2-5tpfa-eWbruUmdHDvYFuD2e3Hqz8btrWMPr7Mbd5da1kY-Kh2iqsPVIsllxL7xenGFhtxHi3Xfqg$> ? > > ... > > We’ve investigated setting the AMSG and NAMSG fields in the record, but suspect that this is intended to be set programmatically? > > The idea is for device support to change to recGblSetSevrMsg() > in places where recGblSetSevr() is used to signal an alarm. > > > int recGblSetSevrMsg(void *precord, > > epicsEnum16 new_stat, > > epicsEnum16 new_sevr, > > const char *msg, ...) > > So printf() format strings can be used, although there is a > limit of 40 characters (aka. DB_AMSG_SIZE). > > > > Thank you in advance for any assistance you can provide, > > > > Ivan Finch > > > > ISIS Controls > > > |