1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025 Index 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
<== Date ==> <== Thread ==>

Subject: Re: Question About ADEuresys XML File Support for the EPICS IOC
From: "Kim, Kuktae via Tech-talk" <tech-talk at aps.anl.gov>
To: Mark Rivers <rivers at cars.uchicago.edu>, "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov>
Date: Mon, 31 Mar 2025 07:44:49 +0000
Hi Mark,

I really appreciate your help with the XML file support for the frame grabber. Unfortunately, our camera is being moved from the test stand to the hutch tomorrow, so I won’t have access to it for a week or two. Once I regain access, I’ll test the new ADGenICam and ADEuresys modules and update you.

Best regards,
Kuktae

From: Mark Rivers <rivers at cars.uchicago.edu>
Sent: Sunday, March 30, 2025 10:27 AM
To: Kim, Kuktae <ktkim at slac.stanford.edu>; tech-talk at aps.anl.gov <tech-talk at aps.anl.gov>
Subject: RE: Question About ADEuresys XML File Support for the EPICS IOC
 

BEWARE: This email originated outside of our organization. DO NOT CLICK links or attachments unless you recognize the sender and know the content is safe.


Hi Kuktae,

 

I have now completed this enhancement. It required the following changes:

  • The Python scripts that generate the database and OPI files in ADGenICam. These now accept an optional 2-letter prefix. The default is GC, which was used previously.
  • The parser in ADGenICam::drvUserCreate. It now allows any 2-letter prefix, not just GC.
  • EuresysFeature class. It is now a template class that uses the GenICam module template parameter.
  • ADEuresys:createFeature(). It now uses the prefix in the drvInfo string to determine which module to use:
    • GC = RemoteModule
    • DV = DeviceModule
    • DS = DataStreamModule
    • IF = InterfaceModule
    • SY = SystemModule

ADGenICam now contains the XML, database, and OPI files for the Euresys TL modules.

 

The release notes for ADGenICam and ADEuresys explain the changes.
https://github.com/areaDetector/ADEuresys/blob/main/RELEASE.md
https://github.com/areaDetector/ADGenICam/blob/master/RELEASE.md

 

These are the new medm screens corresponding to the edm screens in the first post in this thread. Note that now the PVs are showing the actual values of the features and they can be controlled.

image.png (view on web)

image.png (view on web)

 

Please give it a try and let me know of any issues.

 

Mark

 

 

From: Kim, Kuktae <ktkim at slac.stanford.edu>
Sent: Wednesday, March 26, 2025 1:37 PM
To: Mark Rivers <rivers at cars.uchicago.edu>; tech-talk at aps.anl.gov
Subject: Re: Question About ADEuresys XML File Support for the EPICS IOC

 

Hi Mark,

 

Thank you for your detailed explanation and for moving this discussion to a GitHub issue.

 

I really appreciate the insights you've shared on how ADEuresys handles different modules and the potential enhancements to support StreamModule, InterfaceModule, and others more generically.

 

Best regards,

Kuktae

 


From: Mark Rivers <rivers at cars.uchicago.edu>
Sent: Wednesday, March 26, 2025 11:12 AM
To: Kim, Kuktae <ktkim at slac.stanford.edu>; tech-talk at aps.anl.gov <tech-talk at aps.anl.gov>
Subject: RE: Question About ADEuresys XML File Support for the EPICS IOC

 

BEWARE: This email originated outside of our organization. DO NOT CLICK links or attachments unless you recognize the sender and know the content is safe.

 

Hi Kuktae,

 

You raise an interesting question.  The Euresys EGrabber software is nice because grabber it uses GenApi to read and write feature values for both the camera and the frame grabber.

 

For example, integer features on the camera itself are read with this code: https://github.com/areaDetector/ADEuresys/blob/03fdd23dc59118d89863aa3a895c3e108f32d8ee/EuresysApp/src/EuresysFeature.cpp#L81C10-L82C9

 

value = mGrabber->getInteger<RemoteModule>(mFeatureName);

 

Note that getInteger is a template function, where the template defines the module that feature belongs to, RemoteModule in this case.

 

ADEuresys currently handles RemoteModule features in a generic way using this function. https://github.com/areaDetector/ADEuresys/blob/main/EuresysApp/src/EuresysFeature.cpp

 

The features you would like to use are in other modules.  ADEuresys currently handles just a few of those in a non-generic way.  For example, this is the ADEuresys::readStatus function:

 

asynStatus ADEuresys::readStatus()

{

    mGrabber_->setString<StreamModule>("EventSelector", "RejectedFrame");

    epicsUInt64 rejectedFrames = mGrabber_->getInteger<StreamModule>("EventCount");

    setIntegerParam(ESRejectedFrames, (int)rejectedFrames);

    epicsUInt64 CRCErrors = mGrabber_->getInteger<InterfaceModule>("CxpStreamDataPacketCrcErrorCount");

    setIntegerParam(ESCRCErrorCount, (int)CRCErrors);

    epicsUInt64 outputQueue = mGrabber_->getInfo<StreamModule, uint64_t>(GenTL::STREAM_INFO_NUM_AWAIT_DELIVERY);

    setIntegerParam(ESOutputQueue, (int)outputQueue);

  

    return ADGenICam::readStatus();

}

 

Note that it reads features from the StreamModule and InterfaceModule.

 

ADEuresys could be enhanced so that it provides generic support for the StreamModule, InterfaceModule, and other modules.  It would not be too difficult.  The EuresysFeature class would need to be extended so that it knows which module a feature belongs to.  That information would need to be encoded in the link fields of the records that the Python parser produces.  This is an example record for a camera feature that uses the RemoteModule.

 

record(ao, "$(P)$(R)GC_AcqFrameRate") {

  field(DTYP, "asynInt64")

  field(OUT,  "@asyn($(PORT),$(ADDR=0),$(TIMEOUT=1))GC_I_AcquisitionFrameRate")

  field(DISA, "0")

}

 

Note that drvInfo string is GC_I_AcquisitionFrameRate.  “GC” flags that this is a GenICam camera parameter (i.e. RemoteModule), “I” means that it is an integer, and AcquisitionFrameRate is the feature name from the camera XML file.  We could use ST for StreamModule, IN for InterfaceModule, etc. The Python code would need to use those strings when writing the database file, and the GenICam parser would need to understand them and create a GenICam feature with the correct module identifier.

 

I am moving this discussion to a Github issue.  https://github.com/areaDetector/ADEuresys/issues/2

 

Thanks,

Mark

 

From: Tech-talk <tech-talk-bounces at aps.anl.gov> On Behalf Of Kim, Kuktae via Tech-talk
Sent: Monday, March 24, 2025 7:04 PM
To: tech-talk at aps.anl.gov
Subject: Question About ADEuresys XML File Support for the EPICS IOC

 

Hello,

 

I am currently developing an EPICS IOC for the AXIS-SXRF-60 camera and the Euresys Coaxlink CXP-12 Quad Frame Grabber. 

Thanks to ADGenICam and ADEuresys, I’ve been able to save a significant amount of time and effort.

 

Using the Euresys gentl utility, I extracted the XML files for both the camera and the frame grabber as below:

 

$ gentl xml  

$ ls  

6060CXP.xml  

Euresys_Coaxlink_TLDataStream_25_02_0.xml  

Euresys_Coaxlink_TLDevice_25_02_0.xml  

Euresys_Coaxlink_TLInterface_25_02_0.xml  

Euresys_Coaxlink_TLSystem_25_02_0.xml  

 

Next, I used the Python scripts in ADGenICam to generate the EPICS database files and OPI screens from the camera’s XML file. These were saved in:

  • Database templates: ADGenICam/GenICamApp/Db
  • OPI screens: ADGenICam/GenICamApp/op/edl

 

 

I’d like to know if a similar process can be applied to ADEuresys using the XML files from the Euresys frame grabber. 

I created the EPICS database template and OPI screens and placed them in "/ADEuresys/EuresysApp/Db" and "/ADEuresys/EuresysApp/op/edl."

 

However, when I launched the GUI, most of the PVs displayed zero or N.A as below:

 

 

If I can use the database template and GUI in ADEuresys, it would be helpful for troubleshooting and diagnostics.

 

Does anyone know if ADEuresys has plans to support this in the same way as ADGenICam?

 

Thank you for your help!

 

Best regards,

Kuktae

 


Replies:
Re: Question About ADEuresys XML File Support for the EPICS IOC Kim, Kuktae via Tech-talk
References:
Question About ADEuresys XML File Support for the EPICS IOC Kim, Kuktae via Tech-talk
RE: Question About ADEuresys XML File Support for the EPICS IOC Mark Rivers via Tech-talk
Re: Question About ADEuresys XML File Support for the EPICS IOC Kim, Kuktae via Tech-talk
RE: Question About ADEuresys XML File Support for the EPICS IOC Mark Rivers via Tech-talk

Navigate by Date:
Prev: RE: Question About ADEuresys XML File Support for the EPICS IOC Mark Rivers via Tech-talk
Next: Offering used Hytec VME hardware Zimoch Dirk via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025
Navigate by Thread:
Prev: RE: Question About ADEuresys XML File Support for the EPICS IOC Mark Rivers via Tech-talk
Next: Re: Question About ADEuresys XML File Support for the EPICS IOC Kim, Kuktae via Tech-talk
Index: 1994  1995  1996  1997  1998  1999  2000  2001  2002  2003  2004  2005  2006  2007  2008  2009  2010  2011  2012  2013  2014  2015  2016  2017  2018  2019  2020  2021  2022  2023  2024  <2025