2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Very slow reconnection to medm after IOC reboot |
From: | "Ernest L. Williams Jr." <[email protected]> |
To: | Mark Rivers <[email protected]> |
Cc: | Core-Talk <[email protected]> |
Date: | Wed, 04 Feb 2009 07:59:10 -0800 |
Mark Rivers wrote:
Can you say for sure whether beacons are being sent from those systems? It appears that at least part of the problems I am having on my Windows IOCs is that without setting EPICS_CAS_BEACON_ADDR_LIST no beacons were being sent. Once I set this, then preliminary tests show much faster reconnects.
Normally, there would be a default setting for "EPICS_CAS_BEACON_ADDR_LIST"Did casr(1) show what the beacon list was doing before you made the change?
-- Ernest
Mark -----Original Message-----From: Eric Norum [mailto:[email protected]] Sent: Wednesday, February 04, 2009 8:50 AMTo: Mark Rivers Cc: Jeff Hill; Andrew Johnson; Core-Talk Subject: Re: Very slow reconnection to medm after IOC rebootJust for the record, I see this problem from solaris MEDM sessions to R3.14.10 Coldfire/RTEMS IOCs too. Not all the time, but once in a while, widgets stay white for 3 or 4 minutes after the IOC has completed iocInit().