2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 2002 2003 2004 2005 2006 2007 2008 <2009> 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Very slow reconnection to medm after IOC reboot |
From: | Eric Norum <[email protected]> |
To: | Mark Rivers <[email protected]> |
Cc: | Core-Talk <[email protected]> |
Date: | Wed, 4 Feb 2009 10:25:14 -0600 |
iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:32.848869048 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:32.884383710 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:32.967804726 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:33.264623956 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:33.607595531 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:34.739585154 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:36.020909160 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:38.563700176 iocmpbpm01.aps.anl.gov:5064 2009-02-04 10:20:43.683743449At that point many MEDM screens connected right away, but one took about a minute or so.
Could this be a caRepeater problem? On Feb 4, 2009, at 9:48 AM, Mark Rivers wrote:
Can you say for sure whether beacons are being sent from those systems?It appears that at least part of the problems I am having on my Windows IOCs is that without setting EPICS_CAS_BEACON_ADDR_LIST no beacons werebeing sent. Once I set this, then preliminary tests show much faster reconnects. Mark -----Original Message----- From: Eric Norum [mailto:[email protected]] Sent: Wednesday, February 04, 2009 8:50 AM To: Mark Rivers Cc: Jeff Hill; Andrew Johnson; Core-Talk Subject: Re: Very slow reconnection to medm after IOC reboot Just for the record, I see this problem from solaris MEDM sessions to R3.14.10 Coldfire/RTEMS IOCs too. Not all the time, but once in a while, widgets stay white for 3 or 4 minutes after the IOC has completed iocInit(). -- Eric Norum <[email protected]> Advanced Photon Source Argonne National Laboratory (630) 252-4793
-- Eric Norum <[email protected]> Advanced Photon Source Argonne National Laboratory (630) 252-4793