1994 1995 1996 <1997> 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 <1997> 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Serial Ports on MVME167 Card |
From: | [email protected] |
To: | [email protected] |
Date: | Wed, 04 Jun 1997 18:16:49 +0000 |
Is there any fundamental reason why we don't use the serial ports on the MVME167 Card in Epics? We have successfully used them to control SR570 current amplifiers. It requires a small patch to vxWorks to add an ioctl call to change the number of stop bits. If you have fewer than three serial devices interfaced per IOC (as we have) this allows you to dispense with the MVME162 card and IP modules etc.