1994 1995 1996 1997 1998 1999 <2000> 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 <2000> 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: Hardware to for thermocouple readout |
From: | Mark Rivers <[email protected]> |
To: | [email protected] |
Cc: | [email protected], [email protected] |
Date: | Tue, 25 Apr 2000 17:56:36 -0500 |
> I need to monitor 24 thermocouples. Can someone suggest EPICS supported > hardware for this application. We have support for the Keithley 2000 Digital Multimeter via RS-232 (Hideos and MPF). It has a 9 channel thermocouple plug-in card with an on-board resistance thermometer for cold-junction compensation. You would need 3 of these meters for 24 inputs. There is a 20-channel scanner card, but it does not have cold-junction compensation as far as I know. That may or may not be important for your application. Mark Rivers