1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 <2016> 2017 2018 2019 2020 2021 2022 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 <2016> 2017 2018 2019 2020 2021 2022 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: stream Device I/O error |
From: | Eric Norum <[email protected]> |
To: | "Gofron, Kazimierz" <[email protected]> |
Cc: | "[email protected]" <[email protected]> |
Date: | Thu, 28 Apr 2016 09:35:56 -0700 |
What version of StreamDevice are you using? I’ve got a crate monitor prototype file that assigns to a lot more than four records: query { out "Q"; in ":" "SN=%(\$1Serial.VAL)39[^,]," "UN=%(\$1Name.VAL)39[^,]," "IP=%*[^,]," "V3=%d," "V5=%(\$1VP5.RVAL)d," "V+12=%(\$1VP12.RVAL)d," "V-12=%(\$1VM12.RVAL)d," # "VAUX=%*[^,]," "T1=%(\$1Temp1.VAL)d," "T2=%(\$1Temp2.VAL)d," "T3=%(\$1Temp3.VAL)d," "T4=%(\$1Temp4.VAL)d," "F1=%(\$1Fan1.VAL)d," "F2=%(\$1Fan2.VAL)d," "F3=%(\$1Fan3.VAL)d," "F4=%(\$1Fan4.VAL)d," "F5=%(\$1Fan5.VAL)d," "F6=%(\$1Fan6.VAL)d," "F7=%(\$1Fan7.VAL)d," "F8=%(\$1Fan8.VAL)d," "F9=%(\$1Fan9.VAL)d," "OT=%*[^,]," "OV=%*[^,]," "OC=%*[^,]," "PS1=%(\$1PS1status.VAL)d," "PS2=%(\$1PS2status.VAL)d," "MSG=%*[^,]," "SW=%(\$1PowerSwitch.VAL)d," "PROT=%*[^,]," "I3=%*[^,]," "I5=%*[^,]," "I12=%*[^,]," "I-12=%*[^,]," "CODE=%(\$1Firmware.VAL)39[^,]," "ENET=%*[^,]," "POH=%(\$1HoursOn.VAL)g," "MAXTMP=%(\$1MaxTemp.VAL)g,"; ExtraInput = Ignore;
--
Eric Norum [email protected] |