1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 <2018> 2019 2020 2021 2022 2023 2024 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 <2018> 2019 2020 2021 2022 2023 2024 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: MCA7-7: Problems to read PV mca |
From: | Hugo Slepicka <[email protected]> |
To: | Douglas Henrique C. de Araújo <[email protected]> |
Cc: | [email protected] |
Date: | Tue, 08 May 2018 19:42:53 +0000 |
Hi,
I installed the support mca7-7 to use a X-123SDD Detector using the MCA
Amptek Driver. The IOC starts correctly and the medm screen Amptek.adl
works perfectly, but I'm having problem to read a PV mca1.
In the medm screen mca.adl the graph don't show any data and return the
follow message: The requested data transfer is greater than available
memory or EPICS_CA_MAX_ARRAY_BYTES. If I use "caget" in this PV, I have
the same problem.
But, if I limit the number of elements of array until 4095 using: caget
-# 4095 mcaTest:mca1 for example, the pv return a correct value.
I put a very high value in variable
EPICS_CA_MAX_ARRAY_BYTES="999999999999", but it still didn't work.
Has anyone had this kind of problem? Any idea how to debug/solve this?
Best Regards
--
Douglas Henrique C. de Araujo
Software de Operação das Linhas de Luz
Laboratório Nacional de Luz Síncrotron – (LNLS)
Centro Nacional de Pesquisa em Energia e Materiais (CNPEM)
[email protected] | +55 (19) 3512 1228
www.lnls.br