1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: Delta Tau issue |
From: | "Knap, Giles \(DLSLtd,RAL,LSCI\) via Tech-talk" <tech-talk at aps.anl.gov> |
To: | Mark Rivers <rivers at cars.uchicago.edu>, Andy Foster <ajf at observatorysciences.co.uk> |
Cc: | tech-talk <tech-talk at aps.anl.gov> |
Date: | Tue, 26 Jul 2022 09:05:46 +0000 |
I just noticed that the instructions fail to say that you can install and run with:
From: Knap, Giles (DLSLtd,RAL,LSCI) <giles.knap at diamond.ac.uk>
Sent: 26 July 2022 10:02 To: Mark Rivers <rivers at cars.uchicago.edu>; Andy Foster <ajf at observatorysciences.co.uk> Cc: tech-talk <tech-talk at aps.anl.gov> Subject: Re: Delta Tau issue
Mark,
You may also find that this command will clear the error.
clrf
(Which means clear fault)
For a GUI tool that lets you send arbitrary commands and also shows the status bits see https://dls-controls.github.io/dls-pmac-control
From: Tech-talk <tech-talk-bounces at aps.anl.gov> on behalf of Andy Foster via Tech-talk <tech-talk at aps.anl.gov>
Sent: 25 July 2022 22:43 To: Mark Rivers <rivers at cars.uchicago.edu> Cc: tech-talk <tech-talk at aps.anl.gov> Subject: Re: Delta Tau issue Hi Mark,
My understanding of this is that a checksum error has occurred in downloading a program such as a PLC or motion program to the PMAC user buffer space. I think it can also be caused by a download of the firmware, but since you don't do that very
often, if ever, unlikely to be that.
In my experience, it needs a power cycle of the logic power to clear that bit.
Cheers, Andy
On Mon, 25 Jul 2022, 21:25 Mark Rivers via Tech-talk, <tech-talk at aps.anl.gov> wrote:
-- This e-mail and any attachments may contain confidential, copyright and or privileged material, and are for the use of the intended addressee only. If you are not the intended addressee or an authorised recipient of the addressee please notify us of receipt by returning the e-mail and do not use, copy, retain, distribute or disclose the information in or attached to the e-mail. |