1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 <2022> 2023 2024 2025 |
<== Date ==> | <== Thread ==> |
---|
Subject: | RE: PINI field not working with modbus |
From: | Mark Rivers via Tech-talk <tech-talk at aps.anl.gov> |
To: | "Marco A. Barra Montevechi Filho" <marco.filho at lnls.br>, "tech-talk at aps.anl.gov" <tech-talk at aps.anl.gov> |
Date: | Tue, 26 Jul 2022 23:08:34 +0000 |
Hi Marco, Your observations here are easy to explain. There are 2 types of messages: These are the messages from drvModbusAsyn::readInt32(): 2022/07/26 18:41:19.114 drvModbusAsyn::readInt32 port NEG_EMODBUS_1_1_Rd_VTarget function=0x3, offset=00, value=0x4b0 2022/07/26 18:41:20.114 drvModbusAsyn::readInt32 port NEG_EMODBUS_1_1_Rd_VTarget function=0x3, offset=00, value=0x4b0 They are printed at this line in the driver: They occur at 1 Hz because that is the scan rate of the TargetVoltRead record. They do not occur if you set the record scan to Passive. The readInt32 function is just returning the value from the last poll done by the driver, it does
not actually do any Modbus I/O. These are the messages from drvModbusAsyn::doModbusIO(): 2022/07/26 18:41:19.583 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:41:20.631 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS Those are printed at this line in the driver: They also occur about every 1 second. That must be because that is the value of the macro argument $(MBUS_POLL) that you used in the following command. That is the poll_ms argument of drvModbusAsynConfigure(). I don’t think you shared
the line which sets the value of MBUS_POLL. drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_VTarget", "EMODBUS", ${MBUS_SL_ADDR},${MBUS_READ},0x3000,1,0,${MBUS_POLL}, ""); The driver is polling the device every MBUS_POLL ms. That is why you see those messages even when the record is Passive. There could be many records using the registers that are read by the NEG_EMODBUS_1_1_Rd_VTarget port driver. Some
might have SCAN=Passive, some might have SCAN=1 second, and some might have SCAN=I/O Intr. The poller therefore needs to always be running, since it does not know when you might change a record to SCAN=I/O Intr, and also because it is more efficient to read
a large block of registers rather than multiple individual calls. Mark From: Marco A. Barra Montevechi Filho <marco.filho at lnls.br>
Adding a few things i found out, if it helps in anything: I added
record(ai,
"${BL}:${H}:${EQ}:TargetVoltRead"){
field(DESC,
"Voltage set on target [V].")
field(DTYP,
"asynInt32")
field(EGU,
"V")
field(ASLO,
0.01)
field(INP,
"@asyn(NEG_EMODBUS_1_1_Rd_VTarget,0,1000)MODBUS_DATA")
field(SCAN,
"1 second")
field(PINI,
"YES")
field(PRIO,
"LOW") } i run the st.cmd and get constant 1-second-periodic updates such as: #create_monitor_set("/usr/local/epics/apps/config/NEG/NEG_save_restore.req", 5, "BL=${BL}, H=${H}, EQ=${EQ}") ## Start any sequence programs #seq sncxxx,"user=gabrielfedelHost" epics> 2022/07/26 18:41:18.535 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:41:18.535 drvModbusAsyn::readInt32 port NEG_EMODBUS_1_1_Rd_VTarget function=0x3, offset=00, value=0x4b0 2022/07/26 18:41:19.114 drvModbusAsyn::readInt32 port NEG_EMODBUS_1_1_Rd_VTarget function=0x3, offset=00, value=0x4b0 2022/07/26 18:41:19.583 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:41:20.114 drvModbusAsyn::readInt32 port NEG_EMODBUS_1_1_Rd_VTarget function=0x3, offset=00, value=0x4b0 2022/07/26 18:41:20.631 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS and so on... #create_monitor_set("/usr/local/epics/apps/config/NEG/NEG_save_restore.req", 5, "BL=${BL}, H=${H}, EQ=${EQ}") ## Start any sequence programs #seq sncxxx,"user=gabrielfedelHost" epics> 2022/07/26 18:44:34.525 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:44:35.567 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:44:36.602 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:44:37.650 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS 2022/07/26 18:44:38.697 drvModbusAsyn::doModbusIO port NEG_EMODBUS_1_1_Rd_VTarget READ_REGISTERS From: Marco A. Barra Montevechi Filho <marco.filho at lnls.br> Of course! drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_VTarget",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x3000,1,0,${MBUS_POLL},
"");
#!/home/marco/work/cnpem_git/LCI/NEGPowerMINI/bin/linux-x86_64/NEG < /home/marco/work/cnpem_git/LCI/NEGPowerMINI/iocBoot/iocNEG/envPaths epicsEnvSet("BL","LCI") epicsEnvSet("H","X") epicsEnvSet("EQ","NEGPowerMINI") epicsEnvSet("IOCNAME","NEG") # Configuração da linha de luz < /home/marco/work/cnpem_git/LCI/NEGPowerMINI/iocBoot/iocNEG/NEG.config epicsEnvSet("STREAM_PROTOCOL_PATH","${TOP}/db") cd ${TOP} ## Register all support components dbLoadDatabase "dbd/NEG.dbd" NEG_registerRecordDeviceDriver pdbbase drvAsynIPPortConfigure("EMODBUS","10.20.41.90:502",0,0,1) ########NOT USED ANYMORE. KEEPING FOR HISTORICAL REASONS### # Set up ASYN HYPPIE ports # pxiCreateSM(asyn, shared memory name) # drvasynPXIConfig(port, COM port, shared memory name, serial type)
#asynSetOption("EMODBUS", 0, "${BAUD}", "9600")
#asynSetOption("EMODBUS", 0, "bits", "8") #asynSetOption("EMODBUS", 0, "parity", "none")
#asynSetOption("EMODBUS", 0, "stop", "1") ############################################################################### ############################################################################### ## Configure modbusInterposeConfig("EMODBUS",0,3000,0) # drvModbusAsynConfigure(portName, => create a name # tcpPortName, => defined before # slaveAddress, => defined on equipament # modbusFunction, => 3 : Read Holding Register (16-bit) # modbusStartAddress, => adress of register # modbusLength, => the length of data segment # dataType, => default data type # pollMsec, # plcType); => Equipament name, not used drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_SoftwareVersion",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},
0x1000, 1, 2, ${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_HardwareVersion",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x1002,1,2,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_PowerSuppIntState",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2000,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_LoggingState",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2001,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_SysUptime",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2002,2,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_InternalTemperature",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2004,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_PumpTemperature",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2005,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_OutVolt",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2006,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_OutCurr",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2007,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_TimeRunning",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x2008,2,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_Alarms",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x200A,2,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_TempAlarms",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x200C,2,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_WorkTime",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x200E,2,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Rd_VTarget",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_READ},0x3000,1,0,${MBUS_POLL},
""); drvModbusAsynConfigure("NEG_EMODBUS_1_1_Wr_VTarget",
"EMODBUS",
${MBUS_SL_ADDR},${MBUS_WRITE},0x3000,1,0,${MBUS_POLL},
"");
## Load record instances dbLoadRecords("db/dbNEG.db",
"BL=${BL}, H=${H},
EQ=${EQ}") cd ${TOP}/iocBoot/${IOC} iocInit
From: Mark Rivers <rivers at cars.uchicago.edu> Hi Marco, Can you show us how the NEG_EMODBUS_1_1_Rd_VTarget port is configured? Mark From: Tech-talk <tech-talk-bounces at aps.anl.gov>
on behalf of Marco A. Barra Montevechi Filho via Tech-talk <tech-talk at aps.anl.gov> Hello all. record(ai,
"${BL}:${H}:${EQ}:TargetVoltRead"){
field(DESC,
"Voltage set on target [V].")
field(DTYP,
"asynInt32")
field(EGU,
"V")
field(ASLO,
0.01)
field(INP,
"@asyn(NEG_EMODBUS_1_1_Rd_VTarget,0,1000)MODBUS_DATA")
field(SCAN,
"1 second") }
record(ai,
"${BL}:${H}:${EQ}:TargetVoltRead"){
field(DESC,
"Voltage set on target [V].")
field(DTYP,
"asynInt32")
field(EGU,
"V")
field(ASLO,
0.01)
field(INP,
"@asyn(NEG_EMODBUS_1_1_Rd_VTarget,0,1000)MODBUS_DATA")
field(SCAN,
"Passive")
field(PINI,
"YES") }
Aviso Legal: Esta mensagem e seus anexos podem conter informações confidenciais e/ou de uso restrito. Observe atentamente seu conteúdo e considere eventual consulta ao remetente antes
de copiá-la, divulgá-la ou distribuí-la. Se você recebeu esta mensagem por engano, por favor avise o remetente e apague-a imediatamente. Disclaimer: This email and its attachments may contain confidential and/or privileged information. Observe its content carefully and consider possible querying to the sender before