1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 <2025> | Index | 1994 1995 1996 1997 1998 1999 2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010 2011 2012 2013 2014 2015 2016 2017 2018 2019 2020 2021 2022 2023 2024 <2025> |
<== Date ==> | <== Thread ==> |
---|
Subject: | Re: [EXTERNAL] Problems with the alarm-server and large number of channels |
From: | Charles Jenkins via Tech-talk <tech-talk at aps.anl.gov> |
To: | "Hartman, Steven" <hartmansm at ornl.gov> |
Cc: | Phoebus Tech Talk <tech-talk at aps.anl.gov> |
Date: | Thu, 26 Jun 2025 14:05:49 -0500 |
Hi Merrill—
Are both of your IOCs running on the same computer, and are you using that server’s IP address to specify the CA address list for your Phoebus configuration?
I suspect the problem may be your channel access network configuration. See https://docs.epics-controls.org/en/latest/sys-admin/configure-ca.html for "Multiple IOCs on the same computer”.
The simplest solution is to specify a broadcast address instead. I believe the relevant phoebus preference is "org.phoebus.pv.ca/addr_list"
On Jun 26, 2025, at 10:01 AM, Charles Jenkins via Tech-talk <tech-talk at aps.anl.gov> wrote:
This Message Is From an External SenderThis email was sent from a non-ORNL address. If suspicious, use the Report Phish button in Outlook.Hello Everyone, I am working on setting up the Phoebus alarm-server for the Mu2e experiment. I have a simulated EPICS IOC that I use to develop a Phoebus alarm-server (this includes setting up zookeeper and kafka). I have been able to successfully set up the alarm server for one large sub-system, but when I add a second large sub-system I get "UNDEFINED/Disconnected" messages for process variables on the alarm tree and "UNDEFINED" for these process variables in the alarm table. If I include just one of these large subsystems I do not get these messages. Messages from the alarm-server itself says "connection timed out" for the channels. If I type "ls" in the alarm-server terminal, these alarm topics say "UNDEFINED" . Meanwhile a "caget"of channels from EPICS (the simulated IOC) gives values that I had set previously before starting the alarm-server and Phoebus. Can anyone provide a clue as to what I am not setting up correctly? Thanks, Merrill Jenkins -- +++++++++++++++++++++++++ Merrill Jenkins Professor of Physics ==== Mailing Address ==== Physics 411 University Blvd. N. MSPB RM 115 Mobile, AL 36688 phone 251.414.8013 Dept: 251.460.6224 Fax: 251.460.6800