Chris,
> sorry, another problem for which we would like some advice. In running
> channel access from the Vax and setting a callback on a PV we have noticed
> that if the PV gets changed very quickly in the state code we get the wrong
> value back to the Vax (apparently at least).
When a field in the database is modified and a CA client has registered
an event call back for that field then the value, time stamp, and alarm
information are all pushed onto a queue. Next, the server is
notified by setting a semaphore. The, typically lower priority,
CA server runs when higher priority labor has completed. The
server sequentially converts each item in the queue and sends a
corresponding event message to the client. This procedure ensures
that the clients will see transient changes to a process variable
even if there are short bursts of CPU and network saturation.
It is important to offload the labor required to interface with external
CA clients from the high priority database scan tasks.
Is the native type of the field you are monitoring a string? This will
be the case when you are using the VAL field of a state record.
If so you should know that the CA server event system does not queue up
changes to string fields. The event system also does not queue up changes
to array fields. This is due to memory consumption constraints in the
IOCs. In this case the server will send the value present in the
database when the server dispatches the event message (not necessarily
the value present in the database when the event was triggered).
Regards
Jeff
______________________________________________________________________
Jeffrey O. Hill Internet [email protected]
LANL MS H820 Voice 505 665 1831
Los Alamos, NM USA 87545 FAX 505 665 5107
- Navigate by Date:
- Prev:
Re: OMS VME-8 motor controllers: PAL upgrades Joseph P. Sullivan
- Next:
Re: vxWorks Carl W. Cork
- Index:
<1994>
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024
- Navigate by Thread:
- Prev:
Re: OMS VME-8 motor controllers: PAL upgrades Joseph P. Sullivan
- Next:
Re: symbol tables and incremental run time loading winans
- Index:
<1994>
1995
1996
1997
1998
1999
2000
2001
2002
2003
2004
2005
2006
2007
2008
2009
2010
2011
2012
2013
2014
2015
2016
2017
2018
2019
2020
2021
2022
2023
2024